TOHO ELECTRONICS TTM200 User Manual

Page 203

Advertising
background image

48-7009-E

6-55

■ Output 1 and 2 transmission output function setting

SEt05

oUt1

to

SEt06

oUt2

Setting content

Initial value

11

tRN1

tRN2

Transmission content selection

tRN1=01

tRN2=01

*1

PV (measurement value) output

*2

SV (setting value) output

*3

MV 1 (primary control operating amount) output

*4

MV 2 (secondary control operating amount) output

*5

Control SV (Setting Value) output

3

Forward/reverse operation selection

0*

Forward operation

1*

Reverse operation

Set the output content of transmission output.
The output 1 or output 2 being set for analog output can be used as a transmission output.
For using the output 1 or 2 as a transmission output, set 17 (transmission output) for the target connection of the output 1 or 2.

The transmission output is a function that delivers power of the conditions of the measurement value (PV), setting value (SV),

primary control operating amount (MV 1) , secondary control amount (MV 2) and the control SV (SV Setting Value ) output

with either the voltage or current signal (designated by model assignment upon order).

Also, by setting the movement to either forward or reverse, the voltage or current signal can also be made to move forward or

reverse.



Example: When transmitted in the following setting

Output 1

Output 2

Output type

Current 4 - 20 mADC

Current 4 - 20 mADC

Output target connection setting

o1F=17

o2F=17

Transmission output function setting

tRN1=03

tRN2=13


0

20

-10%

100%

MV transmission (forward operation)
MV transmission (reverse operation)

Output current [mA]

Operating amount [%]

4