TOHO ELECTRONICS TTM200 User Manual

Page 178

Advertising
background image

48-7009-E

6-30

■ Primary control off-point position selection setting

SEt04

CNt

Setting content

Initial value

32

CMod

0

SV unit setting

0

1

Upper

2

Middle

3

Lower

Set the primary control off-point position selection.
Set the selection setting to “0” for allowing to set the off-point position of sensitivity in the SV setting unit of °C and such.
Set the selection setting to “1” to “3” for automatically setting the off-point position of the primary control to upper, middle or
lower position with respect to SV.


<Reverse operation>

Cmod = 0 (SV)

C1

CP1

CP2

C2

+db

ON

OFF

PV

Low

SV

High

Cmod = 1 (upper)

C1

db

C2

ON

OFF

PV

Low

SV

High

Cmod = 2 (middle)

C1

db

C2

ON

OFF

PV

Low

SV

High

Cmod = 3 (lower)

C1

db

C2

ON

OFF

PV

Low

SV

High

C1: Sensitivity setting 1
C2: Sensitivity setting 2
CP1: Off-point setting 1 = negative value
CP2: Off-point setting 2 = positive value
db: Dead band = positive value

C1: Sensitivity setting 1
C2: Sensitivity setting 2
db: Dead band = positive value

C1: Sensitivity setting 1
C2: Sensitivity setting 2
db: Dead band = positive value

C1: Sensitivity setting 1
C2: Sensitivity setting 2
db: Dead band = positive value