■ Star connection

Example: Where 3 heaters of 200 V and 2 kW are used

[When normal]

To equipment
CT input

To equipment
CT input

Load

Load

Load

Normal current is 5.8 A {≒10 A × (1/√3)} for each phase.


[When disconnected in between phases]

To equipment
CT input

To equipment
CT input

Load

Load

Load

Disconnected

Current when disconnected in between phases = 10 A Ч (1/√3) Ч (√3/2) = 5A


[When disconnected on load side]

To equipment
CT input

To equipment
CT input

Load

Load

Load

Disconnected

Current when disconnection occurs on the load side = 10 A Ч (1/√3) Ч (√3/2) = 5A


The CT 1 abnormal current value setting value for this connection is 5.4 A {= (5.8 + 5)/2}.