■ Setting example 3: Bank automatic switching function setting mode (when the program run function is

also used)

This example shows use of both the program run and eight banks for the bank automatic switching
function. The “designated bank” setting for a program run is ineffective in a bank automatic
switching function run. The bank designation according to the bank automatic switching function is
always prioritized over others.

Note Note that the SET 22 [St1bK to St8bK] step* designated bank setting is not also displayed.

SV

SLH

PM7

PM6

PM5

PM4

PM3

PM2

PM1

SLL

SV
value

PM7≦
<SLH

SLL≦
<PM1

PM1≦
<PM2

PM2≦
<PM3

PM3≦
<PM4

PM4≦
<PM5

PM5≦
<PM6

PM6≦
<PM7

SET 20
setting value

M

a

x

.

1

6

p

a

ra

m

e

te

rs

Max. 8 banks

Bank 0

Bank 1

Bank 2

Bank 3

Bank 4

Bank 5

Bank 6

Bank 7

RMP

RMP

10

RMP

10

RMP

10

RMP

10

RMP

5

RMP

5

RMP

10

P1

3.0

P1

4.0

P1

4.0

P1

4.0

P1

4.0

P1

2.0

P1

2.0

P1

4.0

I

0

I

20

I

20

I

20

I

20

I

10

I

10

I

20

D

0

D

5

D

5

D

5

D

5

D

2

D

2

D

5

STEP1

STEP2

STEP3

STEP4

STEP5

STEP6

STEP7

STEP8

SV1

50

C

SV2

100

C

SV3

150

C

SV4

200

C

SV5

150

C

SV6

100

C

SV7

150

C

SV8

20

C

TIM1

00:30

TIM2

00:40

TIM3

00:50

TIM4

01:00

TIM5

00:30

TIM6

00:40

TIM7

00:50

TIM8

02:10

Run start

Run stop

Zone threshold
setting

Temperature

change pattern

Bank 7

Bank 6

Bank 5

Bank 4

Bank 3

Bank 2

Bank 1

Bank 0

Refer

SET 22

setting value

Step SV setting

Step time setting

Step bank setting

Max. 8 steps

STOP operation

Run end

Ineffective when the bank automatic switching function is used

The designated bank is automatically switched according to the bank automatic switching source
value.