TOHO ELECTRONICS TTM200 User Manual

Page 184

Advertising
background image

48-7009-E

6-36

■ Secondary control operating amount limiter upper limit

SEt04

CNt

Setting content

Initial value

42

MLH2

Digital output
MLL 2 to 100.0 (%)

100.0

Analog output
MLL 2 to 110.0 (%)

Set the secondary control operating amount limiter upper limit.

A limit is set for the upper limit of the operating amount calculated.

Output

Operating amount

limiter upper limit

50 %

100%

0%

■ Secondary control operating amount limiter lower limit

SEt04

CNt

Setting content

Initial value

43

MLL2

Digital output
0.0 to MLH 2 (%)

0.0

Analog output
-10.0 to MLH 2 (%)

Set the secondary control operating amount limiter lower limit.

A limit is set for the lower limit of the operating amount calculated.

Output

Operating amount

limiter lower limit

50 %

100%

0%