TOHO ELECTRONICS TTM200 User Manual

Page 208

Advertising
background image

48-7009-E

6-60

6: Start and Stop of the timer operation, which is set in “function setting - DI 1 to 4 start” for timers 1 to 3 (see SET 14 to 16 on page

6-59, are switched over.

Stopping the timer during operation results to midway termination (state of control stop or event output OFF).

Note Setting with DI supersedes the setting change of “communication” or “FUNC key.”

Note Setting the function setting to the bank switchover may cause high-speed switchovers of banks when setting the DI function

setting to a bank.

To solve this phenomenon, delete DI function setting DIF from the bank setting, set DIF to the bank switchover setting, and
put the DIF into the bank.

Note Choose the open collector output when change DI by the event output.

7: CONSTANT OPERATION / PRGRAM MODE SWITCHING

3

Switching between the Constant Operation and the Program Mode will be made

8: STEP FORWARD

3

steps can be forwarded during the program mode.

NOTE: This function is effective only when the Program Mode is being selected.

9: PAUSE

3

By pressing the FUNC-key, the Program Operation can be stopped temporarily.

Switching between Pause – In Operation will be made.

NOTE: This function is effective only when the Program Mode is being selected.

A: Inter-Lock

3

When the "DI = Non-Active", the Control Mode can be stopped forcibly.

Its priority is the highest over all the Control Mode Condition.

The setting of Control Mode Condition can be switched with (SEt04 Md)(SEt03 FU*)(SEt13 DIF).

NOTE: During Constant Operation Mode

When dIF=A, at the same time, the function-key function is set to FU1 – 5 = 2, to re-start the operation after DI=Active,

press function key.

NOTE: During the Program Mode

With DI=Non-Active, it will forcibly go back to “Pre-Operation Condition”. Re-start the operation after DI=Active.