TOHO ELECTRONICS TTM200 User Manual

Page 255

Advertising
background image

48-7009-E

7-24

7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (2/2)

Setting data

Character

Setting (monitor) value

Initial value

Unit

Setting

value

Blind

Event lower limit

E3L
E4L
E5L
E6L
E7L

Temperature: -1999.9 to 2999.9

-1999 to 2999

Note that, for thermocouples R, S
and B, the value of WRe 5-26 or
PR 40-20 is -1999 to 9999.
Analog: -19999 to 29999

0


C


Digit

Event sensitivity

E3C
E4C
E5C
E6C
E7C

Temperature: 0.0 to 999.9

0 to 999

Analog: 0 to 9999

0

C

Digit

Event delay timer

E3t
E4t
E5t
E6t
E7t

0 to 9999

0

Second

Event function 2 (PV
abnormality)

E3F2
E4F2
E5F2
E6F2
E7F2

Function
**0: Nonexistent
**1: Existent
Add-on function
*0*: None
*1*: Hold
*2*: Delay
*3*: Hold + delay
Control mode interlocking function
0**: All modes
1**: RUN/MAN mode only
2**: RUN mode only

000

None

Event function 3
(CT abnormality)

E3F3
E4F3
E5F3
E6F3
E7F3

Function
**0: Nonexistent
**1: CT 1 abnormality
**2: CT 2 abnormality
**3: CT 1 abnormality + CT 2
abnormality
Add-on function
*0*: Nonexistent
*1*: Hold
*2*: Delay
*3*: Hold + delay
Control mode interlocking function
0**: All modes
1**: RUN/MAN mode only
2**: RUN mode only

000

None

Event function 4
(loop abnormality)

E3F3
E4F3
E5F3
E6F3
E7F3

Function
*0: Nonexistent
*1: Existent
Add-on function
0*: Nonexistent
1*: Hold

00

None

Event polarity

E3P
E4P
E5P
E6P
E7P

0: Normal open
1: Normal close

00

None