Remote display protocol [remote display, Pr 5230 instrument manual commissioning – Rice Lake PR5230 Fieldbus Transmitter User Manual
Page 141
PR 5230 Instrument Manual
Commissioning
Sartorius
EN-141
Remote display protocol [Remote display]
Select the serial interface to which the remote display is connected and then select [Param] to define the
[Baudrate] and the remote display type [Mode] connected.
Press
to select the specific parameter.
Press
to select the respective values.
The light gray displayed parameter cannot be changed.
Setup/Serial ports/
Builtin RS485
Assigned to
Remote display
Protocol
Remote display
Baudrate
9600 bd 300, 600, 1200, 2400, 4800, 9600, 19200
Bits
7
Parity
even
Stopbits
1
Mode
multiple transmitters Several remote displays are connected.
Device ID
A Address of the instrument
Next Device ID
B Next address of the instrument
If only 1 instrument is connected to a remote display (normal case), [Mode] must be set to [single transmitter].
For PR 1577 remote display [PR 1577 mode] has to be set.
If more than 1 instrument is connected to 1 remote display, [Mode] must be set to [multiple transmitters].
At [Device Id] the own instrument address (A, B, C ...) has to be entered, at [Next Device Id] the address of the
subsequent instrument has to be entered
Press
to return to the menu ‚Serial ports’.