PR 5230 Instrument Manual

Options

Sartorius

EN-33

3.2.8.3

Potential-free Load Cell Supply Voltage

The instrument with option WE1 will be delivered with an intrinsically safe circuit which is galvanically
connected with the equipotential bonding (PA).
















Jumper

J250


At distances >50 m a potential-free load cell supply voltage is required. This is done as follows:
• Cut the jumper J250 on the weighing electronics board.
• Turn the remaining wire leads upward and cut them just above the board. Make sure that both contacts

have a minimum distance of 2 mm and don’t touch other potentials.

If the jumper

J250 is open, the intrinsically safe circuit is isolated from the housing (PA) at a minimum test

voltage of 500 V.