Adapting the analog output, Pr 5230 instrument manual commissioning – Rice Lake PR5230 Fieldbus Transmitter User Manual

Page 159

Advertising
background image

PR 5230 Instrument Manual

Commissioning

Sartorius

EN-159

5.10.1

Adapting the Analog Output

The output current can be adapted in small ranges. This is required, if small deviations from the nominal value
occur in a connected PLC.

Press

-[Show HW-slots] to open the menu:

Info/

HW-Slots

Builtin

RS485

Builtin

RS232

Builtin

analog out

Builtin

Digital i/o

PR1721/45

CC-Link

PR5230/xx

ADC

Press to select [analog out].

Info/

HW-Slots

Builtin

analog out

In use by PLC task

2

Analog output

0.000 mA

counts

12 cnt

Stop PLC Stop I/O Adjust

Reset

Press [Adjust]


Adapt analog output ?

Safety prompt: Reply [Yes] to start adapting.

Info/HW-Slots/

Adjust Analog Output

Output

4.000 mA

Measured

4.004 mA

Enter e.g. the value for 4 mA measured by the connected PLC under [Measured].
After pressing

, the 2nd value (20 mA) is displayed:

Info/HW-Slots/

Adjust Analog Output

Output

20.000 mA

Measured

20.010 mA

Enter e.g. the value for 20 mA measured by the connected PLC under [Measured].

Advertising