PR 5230 Instrument Manual
Options
Sartorius
EN-37
3.2.10.5
Load Cells
Supply voltage
±6 V DC (nominal)/
≤96 mA
Max. 4 load cells of 650
Ω each, connected in
parallel (= 162.5 ¥)
±3.6 V DC (nominal)/
≤96 mA Max. 8 load cells of 650 Ω each, connected in
parallel (= 81.3 ¥)
or
4 load cells of 350
Ω each, connected in parallel
(= 87.5 ¥)
Tolerance range
±5.8…±6.2 V DC; ±3.4…±3.8 V DC
Max. current
≤100 mA short circuit
Measuring voltage V
meas
Max. 36 mV (differential)
Sense voltage V
sense
±6 V nominal (with ref. to ground)
±3.6 V nominal (with ref. to ground)
3.2.10.6
Connection Cable
Length of the connection cable between junction box and PR 5230
Type
PR 6135, PR 6135A
Max. 200 m – length of the load cell cable
Length of the connection cable between weighing platform and PR 5230
Type
LiYCY
Max. 200 m
3.2.10.7
Environmental Conditions
Use the transmitter only within the temperature range of -10 °C…+40 °C. Avoid the inadmissible exposure of
heat, cold, direct sunlight, UV radiation or vibration. Install the instrument in that way, that air circulation is
possible and heat sources are sufficient far away.