Sartorius

3.2.8.4

Potential Equalization

Possible compensatory currents between several conducting plant sections will be avoid by installing a
potential equalization in the ex areas.

PR5230-WE1-…

Load Cells
Wägezellen

Junction Box
Verbindungskasten

Ex Area Zone 1/21
Ex-Bereich Zone 1/21

Non Ex Area
Kein Ex-Bereich

(1)

(2)

(1)

(1)

(2) (3)

(6)

(6)

(A)

(4)

(4)

(4)

(A)

(A)

(A)

(A)

(A) (A)

(E)

(5)

(B)

(1)

Pos.

Component

Cross-section

(1)

Conductor for additional potential equalization

≥ 4.0 mm² Cu

(2)

Conductor for potential equalization

≥ 6.0 mm² Cu

(3)

Conductor for potential equalization

≥10.0 mm² Cu

(4)

Main conductor for potential equalization

≥10.0 mm² Cu

(5)

Earthing conductor

≥10.0 mm² Cu

(6)

Load cell by-pass

≥10.0 mm² Cu


(A)

Sub potential equalization terminal

(B)

Main potential equalization terminal

(E)

To earth electrode