Function 3 or 4: reading n successive words, Pr 5230 instrument manual j-bus/modbus protocol – Rice Lake PR5230 Fieldbus Transmitter User Manual

Page 171

Advertising
background image

PR 5230 Instrument Manual

J-Bus/ModBus Protocol

Sartorius

EN-171

Function 3 or 4: Reading n Successive Words

Command

Device
address

Function
number

Address of
1st word

Number of
words

1 byte

1 byte

2 bytes

2 bytes

Range

1...127

3, 4

0...63

1...64

Reply

Device
address

Function
number

Number of
bytes

Value of the
words

1 byte

1 byte

1 byte

n bytes


MSB

LSB

MSB

- - - - - -

MSB

LSB

1

st

word

last word

If the address of one of the words to be read is out of the permissible range (0...63), an error message is sent as
a reply (the address plus the number of bytes must not exceed 64).
Example of function 3 for reading a gross weight (D8 = W16) of 893 kg with ModBus-RTU:
Command

1

3

0

16

0

2

CRC CRC

Reply

1

3

4

0

0

3

125 CRC CRC

Example with ModBus-TCP:
Command

47

12

0

0

0

6

0

3

0

16

0

2

Reply

47

12

0

0

0

7

0

3

4

0

0

3

125

The individual bytes are shown.