PR 5230 Instrument Manual

SMA Protocol

Sartorius

EN-185


Example: 6000 kg x 1 kg platform scale

Command

Reply

<LF> I <CR>

<LF>SMA:2/1.0 <CR>

<LF>N<CR>

<LF>TYP:S <CR>

<LF>N<CR>

<LF>CAP:kg_:6000:1:0 <CR>

<LF>N<CR>

<LF>CMD:HPTMCR <CR>

<LF>N<CR>

<LF>END: <CR>


Example: 5000g x 1 g, 10000g x 2, 25000 g x 5 multiple range/multi-interval

Command

Reply

<LF> I <CR>

<LF>SMA:2/1.0 <CR>

<LF>N<CR>

<LF>TYP:S <CR>

<LF>N<CR>

<LF>CAP:g__:5000:1:0 <CR>

<LF>CAP:g__:10000:2:0 <CR>

<LF>CAP:g__:25000:5:0 <CR>

<LF>N<CR>

<LF>CMD:HPTMCRQ <CR>

<LF>N<CR>

<LF>END: <CR>

7.5

Communication Error

When a communication error due to a parity error or a frame error (if used) was detected, the scale sends an
ASCII ‘!’ character. The only other error is the detection of an unknown or non-supported command. In this
case, an ASCII '?' character is sent as a reply. Dependent on the error messages, the controlling computer must
decide how to continue the scale operation.