4 error messages for asycom commands, Error messages for asycom commands, Asycom protocol – Rice Lake PR5230 Fieldbus Transmitter User Manual

Page 188: Pr 5230 instrument manual

Advertising
background image

Asycom Protocol

PR 5230 Instrument Manual

EN-188

Sartorius

Legend
(<aa> a character in binary code)

m

Memory command, binary

r,w,a,o,s,c

Read, write, AND, OR, set, clear

x,b,w,d

Bit, byte, word, double word

q

Quit

<aa><aa>

Address (high byte, low byte)

<dd>

Data byte

<nn>

Number of data

<0q>

1 bit

<dd>

Several data bytes

In case of error, the reply is

e<xx><yy><zz>, see also Chapter 8.4.

Note:

The addresses in these telegrams are binary.
Die addresses in the list of Chapter 9 are decimal.

8.4

Error Messages for Asycom Commands

Error

Description

Error

Description

E20000

Error in telegram structure

E10010

Arithmetic overflow

E30000

BCC error

E10020

Overload

E40000

Hardware error messages

E10030

ADC hardware error

E50000

Analog test active

E10040

weight > 5 digits

E60000

Wrong address/weighing point

E10050

No weight

E63000

Fixtare > MAX

E10060

No Sense voltage

E70000

Tared weighing point or no standstill

E10070

Exchanged inputs

Advertising