7 pr 1721/45 cc-link interface, Pr 1721/45 cc-link interface, Installing the instrument and plug-in cards – Rice Lake PR5230 Fieldbus Transmitter User Manual
Page 84: Pr 5230 instrument manual
Installing the Instrument and Plug-in Cards
PR 5230 Instrument Manual
EN-84
Sartorius
4.4.7
PR 1721/45 CC-Link Interface
The CC-Link interface PR 1721/45 is a plug-in card for mounting in slot 2, see Chapter 4.4.1.
It contains all functions to provide a complete CC-Link slave with transfer rates up to 10 Mbps.
Internal connection 34- pin connector on flat cable for
slot 2
External connection 5-pin plug-in terminal block
DA DB GND S PE
S = screen
Transfer rate
156; 625 kbps; 2,5; 5, 10 Mbps
Protocol
CRC error detection, 128 I/O bits and
16 (32 bit) words, max. 64 station nodes
Cable
2x 2 shielded twisted pair
Bus termination
110 ¥ at the cable ends
Bus load
100 mA
Configuration
CSP file ‚PR1721_1.csp’
Certificates/
conformity
Type: ABS-CCL (H/W: 1.01, S/W: 2.00.05,
CC-Link: 2.0)
Reference Number 372
Dimensions (LxWxH)
87 x 55 x 15 mm Potential isolation
Yes, optocoupler and DC/DC converter
Weight
125 g
Cable length
100m @ 10 Mbps, 1200m @ 156 kbps
Caution!
Ensure that the three rotary switches (station no. and baud rate) are set to 9. Settings
are made via software.
Note:
The CSP file is stored on the CD (directory ‘Fieldbus’ of the according instrument) supplied
with the unit. The current file is also available for download via the Internet:
http://www.sartorius-mechatronics.com [Downloads].