1 option y2, 1 safety instructions, 2 description – Rice Lake PR5230 Fieldbus Transmitter User Manual

Page 26: 3 marking, 4 outputs, 5 in connection with option w1, 6 in connection with option we1, Option y2, Safety instructions, Description

Advertising
background image

Options

PR 5230 Instrument Manual

EN-26

Sartorius

3.1

Option Y2

3.1.1

Safety Instructions

Caution!
It is essential to observe the safety instruction in Chapter 18.4!

3.1.2

Description

PR 5230 with option Y2 is only suitable for using within Ex areas Zone 2 and 22 (non conductive dust)
according European directive 94/9/EG and related harmonized European standards (see also Chapter 18.4).
The Ex design for Zone 2/22 see Chapter 18.4.

3.1.3

Marking

II 3G Ex nA nC IIC T4
II 3D Ex tD A22 IP6X T80°C
SAG 09ATEX004X

See also Chapter 18.4.

3.1.4

Outputs

With option Y2 are following outputs possible:
-

Opto-decoupled outputs (option DA2): Technical Data see Chapter 16.5.8.2.

-

Relays (option DA1): Only external circuits with voltages up to 60 V AC or 75 V DC are allowed to be

connected to the relays, see Safety Instruction in Chapter 18.4.

3.1.5

In Connection with Option W1

Connected load cells or weighing platforms must be certified for use in Ex areas Zone 2 or Zone 22 and for
load cell supply voltages of more than 13.2 V DC.
When use
-

in Zone 2 observe gas group and temperature class.

-

in Zone 22 observe the allowed surface temperature.

3.1.6

In Connection with Option WE1

The combination Y2 and WE1 is also possible; see Ex design for Zone 2/22 and Zone 1/21 in Chapter 18.4.

Advertising