1 dil switch, 2 status-leds on fieldbus card, 3 status display – Rice Lake PR5230 Fieldbus Transmitter User Manual

Page 82: Display, Legend, Installing the instrument and plug-in cards, Pr 5230 instrument manual

Advertising
background image

Installing the Instrument and Plug-in Cards

PR 5230 Instrument Manual

EN-82

Sartorius

4.4.6.1

DIL Switch

Caution!
The DIL switch settings will not be used.
Make sure that the switches 1…8 are set to position ‘ON’!

Settings will be done in the menu [Setup]-[Fieldbus Parameter].

4.4.6.2

Status-LEDs on Fieldbus Card

Watchdog LED

Meaning

Frequency

Color

Flashing

1 Hz green

Module is initialized and ready for operation.

Flashing

2 Hz green

Module is not initialized.

Flashing

1 Hz red

Check error in ASIC and FLASH ROM, module is defect.

4.4.6.3

Status Display

Requirements

In

-[Display items] the items are configured, see Chapter 5.6.7.

In

-[HW-Slots] PR 1721/44 is selected.

Display

1

2

3

4

LED ---

--- ---

---

1

2

3

4

Lit

- - -:

No function.

Lit

- - -:

Not powered, not online.

Lit

- - -:

No function.

Lit

- - -:

No power to device.

Lit

grn:

Link OK, online, connected.

Lit

grn:

Device operational.

Flashing

grn:

Online, not connected.

Flashing

grn:

Data size > configuration.

Lit

red:

Critical link error.

Lit

red:

Unrecoverable error.

Flashing

red:

Connection timeout.

Flashing

red:

Minor error.

Legend

---

off

red

red

grn

green

Advertising