Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 109: Dcf mechanical data - regular quiet

Advertising
background image

109

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

37

38

39

DCF094TR-15HVWW

DCF096TR-15HWWW

DCF080TR-17GPYY

FreeCooling

Y

Y

Y

Enhance Capital Allowance

N

N

N

Number of Refrigeration Circuits

3

3

3

Cooling Duty - High Airflow EC Fans
Nominal Output - Mechanical

(1)

kW

968.4

988.1

802.7

Nominal Input - Mechanical

kW

330.9

342.8

244.3

EER

(2)

2.79

2.75

3.12

ESEER

4.26

4.18

4.53

SEER

4.09

4.02

4.38

Nominal Output - Free Cooling

kW

755.1

759.8

768.0

Ambient temperature for 100% Free Cooling

(5)

°C

-0.4

-0.7

2.4

Cooling Duty - EC Fans
Nominal Output - Mechanical

(1)

kW

963.1

982.1

803.9

Nominal Input - Mechanical

kW

329.1

341.1

244.7

EER

(2)

2.79

2.75

3.11

ESEER

4.25

4.18

4.53

SEER

4.09

4.02

4.37

Nominal Output - Free Cooling

kW

739.1

743.4

756.0

Ambient temperature for 100% Free Cooling

(5)

°C

-0.7

-0.9

2.2

Cooling Duty - AC Fans
Nominal Output - Mechanical

(1)

kW

945.5

963.5

805.4

Nominal Input - Mechanical

kW

331.6

343.9

248.0

EER

(2)

2.72

2.68

3.08

ESEER

3.96

3.92

4.12

SEER

3.83

3.79

4.00

Nominal Output - Free Cooling

kW

691.3

694.9

718.2

Ambient temperature for 100% Free Cooling

(5)

°C

-1.5

-1.7

1.5

Capacity Steps

%

10-25-35-45-60-70-80-90-100

10-25-35-50-60-70-80-90-100

15-25-40-55-65-80-90-100

Minimum Turndown Ratio

0.11

0.12

0.15

Dimensions (H x W x L)

mm

2682 x 2200 x 9374

2682 x 2200 x 9374

2682 x 2200 x 10506

Weight
Machine

(3)

kg

7965

7995

8090

Operating

kg

9450

9475

9590

Water Volume (Total Internal)

l

1485

1480

1500

Maximum Waterflow

l/s

63.4

83.7

46.1

Minimum Waterflow

l/s

24.0

32.1

17.7

Face Area (Total)

2.38

2.38

2.38

Nominal Airflow - High Airflow EC Fans

m³/s

91.7

91.7

103.9

Nominal Airflow - EC Fans

m³/s

88.2

88.2

99.9

Nominal Airflow - AC Fans

m³/s

78.4

78.4

88.8

Quantity

15

15

17

Maximum Speed - High Airflow EC Fans

rpm

1080

1080

1080

Maximum Speed - EC Fans

rpm

1026

1026

1026

Maximum Speed - AC Fans

rpm

904

904

904

Compressor

Trio + Trio + Trio

Trio + Trio + Trio

Tandem + Trio + Trio

Quantity of Compressors

9

9

8

Oil Charge Volume (Total)

l

3 x 5.3 + 3 x 5.3 + 3 x 5.3

3 x 5.3 + 3 x 5.3 + 3 x 5.3

2 x 5.3 + 3 x 5.3 + 3 x 5.3

Refrigeration
Charge (Total)

kg

37 + 39 + 40

37 + 39 + 40

31 + 37 + 38

Water Inlet / Outlet - Unit

DN150

DN150

DN150

Water Drain / Bleed - Evap

inch

0.5

0.5

0.5

Water System
Minimum System Water Volume

(4)

l

8293

8589

5916

Maximum System Operating Pressure

Bar

10

10

10

(1)

Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol

(2)

EER = DX Cooling Output / (Compressor input power + Fan Input Power),

(3)

Based on standard unit without options, operating weight includes refrigerant charge and water volume.

For unit weights with waterside options fitted please refer to Airedale.

(4)

For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations

(5)

Ambient temperature that full Freecool capacity can be achieved

DCF Mechanical Data - Regular Quiet

Advertising