DCF Electrical Data - Regular Quiet

ELECTRICAL DATA

1

2

3

Unit Data

DCF046DR-07DXY0

DCF048DR-07DPY0

DCF051DR-08DPV0

Nominal Run Amps

(1)

A

298.2

304.8

333.9

Maximum Start Amps

A

534.8

540.1

569.2

Recommended Mains Fuse Size

A

315

355

355

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)

0.0

0

0

Quantity

7

7

8

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

7

7

8

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

7

7

8

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

37.1 / 47.5

59.2 / 47.5

59.2 / 55.2

Quantity

3 + 3

2 + 3

2 + 3

Motor Rating

kW

23.5 / 29.6

36.2 / 29.6

36.2 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

210 / 287

298 / 287

298 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

279.7

281.5

301.9

Reactive power reduction/saving

(4)

kVAr

33.2

40.4

53.1

Maximum Start Amps

A

516.3

516.8

537.2

Recommended Mains Fuse Size

A

315

355

355

Electronic Soft-start
Nominal Run Amps

A

298.2

304.8

333.9

Maximum Start Amps

A

420.0

420.9

450.0

Recommended Mains Fuse

A

315

355

355

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

279.7

281.5

301.9

Maximum Start Amps

A

401.5

397.6

418.0

Recommended Mains Fuse Size

A

315.0

355.0

355.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

14.8

14.8

14.8

Unit Nominal Run Amps

A

312.8

319.5

348.6

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

8.4

8.4

8.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

326.5

333.2

362.4

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

16.4

16.4

16.4

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

13.9

13.9

13.9

Unit Nominal Run Amps

A

309.3

315.8

344.7

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

8.6

8.6

8.6

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

320.0

326.3

354.9

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

16.8

16.8

16.8

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.