ELECTRICAL DATA

173

174

175

Unit Data

DCC070TX-19GPPY

DCC074TX-20GPYY

DCC080TX-19GYYV

Nominal Run Amps

(1)

A

447.8

475.9

504.0

Maximum Start Amps

A

683.1

711.2

740.6

Recommended Mains Fuse Size

A

500

500

560

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

19

20

21

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

19

20

21

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 59.2 / 47.5

59.2 / 47.5 / 47.5

47.5 / 47.5 / 47.5

Quantity

2 + 2 + 3

2 + 3 + 3

3 + 3 + 3

Motor Rating

kW

36.2 / 36.2 / 29.6

36.2 / 29.6 / 29.6

29.6 / 29.6 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 298 / 287

298 / 287 / 287

287 / 287 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

413.6

442.4

471.3

Reactive power reduction/saving

(4)

kVAr

59.3

58.9

58.4

Maximum Start Amps

A

648.9

677.7

707.9

Recommended Mains Fuse Size

A

500

500

560

Electronic Soft-start
Nominal Run Amps

A

447.8

475.9

504.0

Maximum Start Amps

A

563.9

592.0

625.8

Recommended Mains Fuse

A

500

500

560

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

413.6

442.4

471.3

Maximum Start Amps

A

529.7

558.5

593.1

Recommended Mains Fuse Size

A

500

500

560

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

458.9

486.9

515.0

Recommended Mains Fuse Size

A

500

560

560

Motor Rating

kW

6.2

6.2

6.2

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

468.9

496.9

525.0

Recommended Mains Fuse Size

A

500

560

560

Motor Rating

kW

12.1

12.1

12.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

10.2

10.2

10.2

Unit Nominal Run Amps

A

455.9

484.0

512.2

Recommended Mains Fuse Size

A

500

560

560

Motor Rating

kW

6.4

6.4

6.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

463.6

491.7

519.9

Recommended Mains Fuse Size

A

500

560

560

Motor Rating

kW

12.4

12.4

12.4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Extra Quiet