Chillers deltachill™ air cooled and freecool, Introduction, Condenser fans – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 21

Advertising
background image

Chillers

DeltaChill™ Air Cooled and FreeCool

21

Chiller Technical Manual 7267818 V1.4.0_04_2014

Introduction

Condenser Fan and Motor - AC

Axial fan assemblies with finger proof grille and incorporating external rotor AC motor technology, capable of highly

accurate discreet speed control., Discharges air vertically. The fans offer maximum performance whilst keeping sound

levels to a minimum.

Condenser Fans

High Airflow EC Fans

Additional free cooling is available when a high air volume

EC Fan is selected.

This option is only available with the Free cool chiller.

The in built EC fan control module allows for fan

speed modulation from 15-100%, a standard AC fans

modulating range is typically 40-100% of full fan speed.

The EC fan presents superior energy efficiency at full

and reduced fan speed compared to the equivalent AC

fan motor, offering efficiency savings anywhere between

30 to 100% compared with an AC fan.

Fan speeds are factory set depending on sound level

variant.
Standard voltage regulated (VR) fan speed controllers

offer a linear response. By comparison the EC fan is

adjusted on demand via the unit microprocessor with

precision, offering substantial energy savings. The

following illustration shows a comparison of the typical

power input required by each method.

0

20

40

60

80

100

120

0

20

40

60

80

100

120

Fan Speed %

Input Power %

Energy saving Electronically Commutated (EC)

Fan Motor

Each 800 mm diameter fan incorporates on board

electronics with AC / DC Conversion and inverter driven

DC motor control to offer unparalleled high efficiency

levels combined with smooth step-less speed control and

quiet operation.

Sickle blades reduce air turbulence to minimise sound

levels and power consumption whilst maximising

performance.

The long bell mouth design provides improved

aerodynamics, up to 10% more air movement, and an

extended vertical throw of air to reduce the chance of air

re-circulation. As standard the enclosure is complete with

an integral finger proof grille.

The fans offer maximum airflow performance while

keeping sound levels to a minimum.

A mains EMC filter is fitted when the EC fan option is

selected with the unit. The filter is design for convenient

mains connection within the bus bar chamber.

Fan speed of 60%
Voltage regulated input power required 60%
EC input power required 18%

EC (Electronically Commutated) Fan Speed

Control
Voltage Regulated Fan Speed Control

Optional Features

Advertising
This manual is related to the following products: