Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 161: Dcf electrical data extra quiet
![background image](/manuals/370937/161/background.png)
161
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
ELECTRICAL DATA
94
95
96
97
Unit Data
DCF092TX-21HVVV
DCF095TX-21HVVW
DCF097TX-21HVWW
DCF099TX-21HWWW
Nominal Run Amps
(1)
A
578.6
590.8
602.9
615.2
Maximum Start Amps
A
787.0
826.1
838.2
850.5
Recommended Mains Fuse Size
A
630
630
630
670
Evaporator
Immersion Heater Rating
W
250
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
21
21
21
21
Full Load Amps
A
2.5
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
1.27
Condenser Fan - Per Fan (EC)
Quantity
21
21
21
21
Full Load Amps
A
3.9
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
2.56
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2 / 55.2
55.2 / 55.2 / 59.2
55.2 / 59.2 / 59.2
59.2 / 59.2 / 59.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
33.1 / 33.1 / 33.1
33.1 / 33.1 / 36.2
33.1 / 36.2 / 36.2
36.2 / 36.2 / 36.2
Sump Heater Rating
W
140
140
140
140
Start Amps
(2)
A
267 / 267 / 267
267 / 267 / 298
267 / 298 / 298
298 / 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
523.2
537.3
551.5
565.6
Reactive power reduction/saving
(4)
kVAr
92.0
89.7
87.5
85.2
Maximum Start Amps
A
731.6
772.6
786.8
800.9
Recommended Mains Fuse Size
A
630
630
630
670
Electronic Soft-start
Nominal Run Amps
A
578.6
590.8
602.9
615.2
Maximum Start Amps
A
680.2
706.9
719.0
731.3
Recommended Mains Fuse
A
630
630
630
670
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
523.2
537.3
551.5
565.6
Maximum Start Amps
A
624.8
653.4
667.6
681.7
Recommended Mains Fuse Size
A
630
630
630
670
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
35.0
Unit Nominal Run Amps
A
607.1
619.2
631.4
650.1
Recommended Mains Fuse Size
A
630
670
670
670
Motor Rating
kW
16.4
16.4
16.4
20.3
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
35.0
41.5
Unit Nominal Run Amps
A
613.6
625.7
637.9
656.5
Recommended Mains Fuse Size
A
630
670
670
710
Motor Rating
kW
20.3
20.3
20.3
23.9
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
33.2
Unit Nominal Run Amps
A
599.6
611.8
624.1
641.4
Recommended Mains Fuse Size
A
630
670
670
670
Motor Rating
kW
16.8
16.8
16.8
20.7
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
33.2
39.2
Unit Nominal Run Amps
A
604.5
616.8
629.1
646.2
Recommended Mains Fuse Size
A
630
670
670
710
Motor Rating
kW
20.7
20.7
20.7
24.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet