ELECTRICAL DATA

94

95

96

97

Unit Data

DCF092TX-21HVVV

DCF095TX-21HVVW

DCF097TX-21HVWW

DCF099TX-21HWWW

Nominal Run Amps

(1)

A

578.6

590.8

602.9

615.2

Maximum Start Amps

A

787.0

826.1

838.2

850.5

Recommended Mains Fuse Size

A

630

630

630

670

Evaporator
Immersion Heater Rating

W

250

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

21

21

21

21

Full Load Amps

A

2.5

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

1.27

Condenser Fan - Per Fan (EC)
Quantity

21

21

21

21

Full Load Amps

A

3.9

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

2.56

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 55.2 / 55.2

55.2 / 55.2 / 59.2

55.2 / 59.2 / 59.2

59.2 / 59.2 / 59.2

Quantity

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

Motor Rating

kW

33.1 / 33.1 / 33.1

33.1 / 33.1 / 36.2

33.1 / 36.2 / 36.2

36.2 / 36.2 / 36.2

Sump Heater Rating

W

140

140

140

140

Start Amps

(2)

A

267 / 267 / 267

267 / 267 / 298

267 / 298 / 298

298 / 298 / 298

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

523.2

537.3

551.5

565.6

Reactive power reduction/saving

(4)

kVAr

92.0

89.7

87.5

85.2

Maximum Start Amps

A

731.6

772.6

786.8

800.9

Recommended Mains Fuse Size

A

630

630

630

670

Electronic Soft-start
Nominal Run Amps

A

578.6

590.8

602.9

615.2

Maximum Start Amps

A

680.2

706.9

719.0

731.3

Recommended Mains Fuse

A

630

630

630

670

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

523.2

537.3

551.5

565.6

Maximum Start Amps

A

624.8

653.4

667.6

681.7

Recommended Mains Fuse Size

A

630

630

630

670

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

35.0

Unit Nominal Run Amps

A

607.1

619.2

631.4

650.1

Recommended Mains Fuse Size

A

630

670

670

670

Motor Rating

kW

16.4

16.4

16.4

20.3

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

35.0

35.0

41.5

Unit Nominal Run Amps

A

613.6

625.7

637.9

656.5

Recommended Mains Fuse Size

A

630

670

670

710

Motor Rating

kW

20.3

20.3

20.3

23.9

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

33.2

Unit Nominal Run Amps

A

599.6

611.8

624.1

641.4

Recommended Mains Fuse Size

A

630

670

670

670

Motor Rating

kW

16.8

16.8

16.8

20.7

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

33.2

33.2

39.2

Unit Nominal Run Amps

A

604.5

616.8

629.1

646.2

Recommended Mains Fuse Size

A

630

670

670

710

Motor Rating

kW

20.7

20.7

20.7

24.4

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.