ELECTRICAL DATA

7

8

9

Unit Data

DCF053DR-10DPV0

DCF055DR-09DYV0

DCF055DR-10DYY0

Nominal Run Amps

(1)

A

342.1

363.4

342.6

Maximum Start Amps

A

577.4

591.8

579.2

Recommended Mains Fuse Size

A

400

400

400

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

10

9

10

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

10

9

10

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

10

9

10

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 55.2

47.5 / 55.2

47.5 / 47.5

Quantity

2 + 3

3 + 3

3 + 3

Motor Rating

kW

36.2 / 33.1

29.6 / 33.1

29.6 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 267

287 / 267

287 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

308.0

331.8

317.5

Reactive power reduction/saving

(4)

kVAr

56.2

53.5

43.8

Maximum Start Amps

A

543.3

560.2

554.1

Recommended Mains Fuse Size

A

400

400

400

Electronic Soft-start
Nominal Run Amps

A

342.1

363.4

342.6

Maximum Start Amps

A

458.2

477.0

464.4

Recommended Mains Fuse

A

400

400

400

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

308.0

331.8

317.5

Maximum Start Amps

A

424.1

445.4

439.3

Recommended Mains Fuse Size

A

400.0

400.0

400.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

363.3

384.5

363.7

Recommended Mains Fuse Size

A

400

450

400

Motor Rating

kW

12.1

12.1

12.1

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

370.6

391.8

371.0

Recommended Mains Fuse Size

A

400

450

400

Motor Rating

kW

16.4

16.4

16.4

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

357.5

379.0

358.4

Recommended Mains Fuse Size

A

400

450

400

Motor Rating

kW

12.4

12.4

12.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

363.1

384.6

364.1

Recommended Mains Fuse Size

A

400

450

400

Motor Rating

kW

16.8

16.8

16.8

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet