Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 238: Dcc electrical data - regular quiet

Advertising
background image

238

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

ni

ca

l

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

122

123

124

Unit Data

DCC080TR-14GYVV

DCC070TR-16GPPY

DCC077TR-15GYYY

Nominal Run Amps

(1)

A

559.7

466.9

513.9

Maximum Start Amps

A

788.1

702.2

750.5

Recommended Mains Fuse Size

A

630

500

560

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

14

16

15

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

14

16

15

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 55.2 / 55.2

59.2 / 59.2 / 47.5

47.5 / 47.5 / 47.5

Quantity

3 + 3 + 3

2 + 2 + 3

3 + 3 + 3

Motor Rating

kW

29.6 / 33.1 / 33.1

36.2 / 36.2 / 29.6

29.6 / 29.6 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 267 / 267

298 / 298 / 287

287 / 287 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

507.9

425.6

476.3

Reactive power reduction/saving

(4)

kVAr

86.6

69.7

65.7

Maximum Start Amps

A

736.3

660.9

712.9

Recommended Mains Fuse Size

A

630

500

560

Electronic Soft-start
Nominal Run Amps

A

559.7

466.9

513.9

Maximum Start Amps

A

673.3

583.0

635.7

Recommended Mains Fuse

A

630

500

560

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

507.9

425.6

476.3

Maximum Start Amps

A

621.5

541.7

598.1

Recommended Mains Fuse Size

A

630

500

560

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

570.8

478.0

524.9

Recommended Mains Fuse Size

A

630

500

560

Motor Rating

kW

6.2

6.2

6.2

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

580.8

488.0

535.0

Recommended Mains Fuse Size

A

630

560

560

Motor Rating

kW

12.1

12.1

12.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

10.2

10.2

10.2

Unit Nominal Run Amps

A

567.6

474.9

522.0

Recommended Mains Fuse Size

A

630

500

560

Motor Rating

kW

6.4

6.4

6.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

575.1

482.4

529.7

Recommended Mains Fuse Size

A

630

560

560

Motor Rating

kW

12.4

12.4

12.4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Regular Quiet

Advertising
This manual is related to the following products: