Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 135: Dcf electrical data - regular quiet
![background image](/manuals/370937/135/background.png)
135
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
ELECTRICAL DATA
16
17
18
Unit Data
DCF055DR-12DPV0
DCF057DR-12DYY0
DCF058DR-11DYV0
Nominal Run Amps
(1)
A
350.4
350.7
371.6
Maximum Start Amps
A
585.7
587.3
600.0
Recommended Mains Fuse Size
A
400
400
400
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
12
12
11
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
12
12
11
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
Quantity
12
12
11
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 55.2
47.5 / 47.5
47.5 / 55.2
Quantity
2 + 3
3 + 3
3 + 3
Motor Rating
kW
36.2 / 33.1
29.6 / 29.6
29.6 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 267
287 / 287
287 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
314.0
323.6
337.9
Reactive power reduction/saving
(4)
kVAr
59.3
46.9
56.6
Maximum Start Amps
A
549.3
560.2
566.3
Recommended Mains Fuse Size
A
400
400
400
Electronic Soft-start
Nominal Run Amps
A
350.4
350.7
371.6
Maximum Start Amps
A
466.5
472.5
485.2
Recommended Mains Fuse
A
400
400
400
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
314.0
323.6
337.9
Maximum Start Amps
A
430.1
445.4
451.5
Recommended Mains Fuse Size
A
400.0
400.0
400.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
21.2
21.2
Unit Nominal Run Amps
A
365.1
371.8
392.7
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
8.4
12.1
12.1
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
28.5
28.5
Unit Nominal Run Amps
A
371.5
379.1
400.0
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
12.1
16.4
16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
13.9
19.8
19.8
Unit Nominal Run Amps
A
361.0
366.5
387.1
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
8.6
12.4
12.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
19.8
26.9
26.9
Unit Nominal Run Amps
A
365.7
372.1
392.7
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
12.4
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet