Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 135: Dcf electrical data - regular quiet

Advertising
background image

135

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

ELECTRICAL DATA

16

17

18

Unit Data

DCF055DR-12DPV0

DCF057DR-12DYY0

DCF058DR-11DYV0

Nominal Run Amps

(1)

A

350.4

350.7

371.6

Maximum Start Amps

A

585.7

587.3

600.0

Recommended Mains Fuse Size

A

400

400

400

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

12

12

11

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

12

12

11

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

12

12

11

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 55.2

47.5 / 47.5

47.5 / 55.2

Quantity

2 + 3

3 + 3

3 + 3

Motor Rating

kW

36.2 / 33.1

29.6 / 29.6

29.6 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 267

287 / 287

287 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

314.0

323.6

337.9

Reactive power reduction/saving

(4)

kVAr

59.3

46.9

56.6

Maximum Start Amps

A

549.3

560.2

566.3

Recommended Mains Fuse Size

A

400

400

400

Electronic Soft-start
Nominal Run Amps

A

350.4

350.7

371.6

Maximum Start Amps

A

466.5

472.5

485.2

Recommended Mains Fuse

A

400

400

400

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

314.0

323.6

337.9

Maximum Start Amps

A

430.1

445.4

451.5

Recommended Mains Fuse Size

A

400.0

400.0

400.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

14.8

21.2

21.2

Unit Nominal Run Amps

A

365.1

371.8

392.7

Recommended Mains Fuse Size

A

400

400

450

Motor Rating

kW

8.4

12.1

12.1

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

28.5

28.5

Unit Nominal Run Amps

A

371.5

379.1

400.0

Recommended Mains Fuse Size

A

400

400

450

Motor Rating

kW

12.1

16.4

16.4

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

13.9

19.8

19.8

Unit Nominal Run Amps

A

361.0

366.5

387.1

Recommended Mains Fuse Size

A

400

400

450

Motor Rating

kW

8.6

12.4

12.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

26.9

26.9

Unit Nominal Run Amps

A

365.7

372.1

392.7

Recommended Mains Fuse Size

A

400

400

450

Motor Rating

kW

12.4

16.8

16.8

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet