ELECTRICAL DATA
164
165
166
Unit Data
DCC075TX-15GYYY
DCC077TX-16GYYV
DCC072TX-17GPYY
Nominal Run Amps
(1)
A
489.5
516.5
468.6
Maximum Start Amps
A
726.1
744.9
703.9
Recommended Mains Fuse Size
A
560
560
500
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
15
16
17
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
15
16
17
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 47.5 / 47.5
47.5 / 47.5 / 55.2
59.2 / 47.5 / 47.5
Quantity
3 + 3 + 3
3 + 3 + 3
2 + 3 + 3
Motor Rating
kW
29.6 / 29.6 / 29.6
29.6 / 29.6 / 33.1
36.2 / 29.6 / 29.6
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 287 / 287
287 / 287 / 267
298 / 287 / 287
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
459.7
478.9
436.6
Reactive power reduction/saving
(4)
kVAr
53.8
65.8
56.6
Maximum Start Amps
A
696.3
707.3
671.9
Recommended Mains Fuse Size
A
560
560
500
Electronic Soft-start
Nominal Run Amps
A
489.5
516.5
468.6
Maximum Start Amps
A
611.3
630.1
584.7
Recommended Mains Fuse
A
560
560
500
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
459.7
478.9
436.6
Maximum Start Amps
A
581.5
592.5
552.7
Recommended Mains Fuse Size
A
560
560
500
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
500.6
527.6
479.7
Recommended Mains Fuse Size
A
560
560
500
Motor Rating
kW
6.2
6.2
6.2
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
510.6
537.6
489.7
Recommended Mains Fuse Size
A
560
560
560
Motor Rating
kW
12.1
12.1
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.2
10.2
10.2
Unit Nominal Run Amps
A
497.8
524.6
476.8
Recommended Mains Fuse Size
A
560
560
500
Motor Rating
kW
6.4
6.4
6.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
505.5
532.3
484.5
Recommended Mains Fuse Size
A
560
560
560
Motor Rating
kW
12.4
12.4
12.4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Extra Quiet