ELECTRICAL DATA

161

162

163

Unit Data

DCC061DX-16DVW0

DCC065DX-16DWW0

DCC068TX-16GPPY

Nominal Run Amps

(1)

A

402.8

415.0

440.5

Maximum Start Amps

A

638.1

650.3

675.8

Recommended Mains Fuse Size

A

450

450

500

Evaporator
Immersion Heater Rating

W

170

170

250

Condenser Fan - Per Fan (AC)
Quantity

16

16

16

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

16

16

16

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 59.2

59.2 / 59.2

59.2 / 59.2 / 47.5

Quantity

3 + 3

3 + 3

2 + 2 + 3

Motor Rating

kW

33.1 / 36.2

36.2 / 36.2

36.2 / 36.2 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

267 / 298

298 / 298

298 / 298 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

366.8

380.9

407.8

Reactive power reduction/saving

(4)

kVAr

60.6

58.3

57.1

Maximum Start Amps

A

602.1

616.2

643.1

Recommended Mains Fuse Size

A

450

450

500

Electronic Soft-start
Nominal Run Amps

A

402.8

415.0

440.5

Maximum Start Amps

A

518.9

531.1

556.6

Recommended Mains Fuse

A

450

450

500

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

366.8

380.9

407.8

Maximum Start Amps

A

482.9

497.0

523.9

Recommended Mains Fuse Size

A

450

450

500

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

413.9

426.1

451.6

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

6.2

6.2

6.2

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

14.8

14.8

21.2

Unit Nominal Run Amps

A

417.5

429.7

461.6

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

8.4

8.4

12.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

10.2

10.2

10.2

Unit Nominal Run Amps

A

410.7

423.0

448.6

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

6.4

6.4

6.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

13.9

13.9

19.8

Unit Nominal Run Amps

A

413.6

425.9

456.3

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

8.6

8.6

12.4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Extra Quiet