Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf electrical data - regular quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 144
144
Chiller Technical Manual 7267818 V1.4.0_04_2014
Chillers
DeltaChill™ Air Cooled and FreeCool
Te
ch
ni
ca
l
Fr
ee
C
oo
l
ELECTRICAL DATA
43
44
45
Unit Data
DCF095TR-18HVVW
DCF098TR-18HVWW
DCF100TR-18HWWW
Nominal Run Amps
(1)
A
613.4
625.5
637.6
Maximum Start Amps
A
848.7
860.8
872.9
Recommended Mains Fuse Size
A
670
670
670
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
18
18
18
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
18
18
18
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
Quantity
18
18
18
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2 / 59.2
55.2 / 59.2 / 59.2
59.2 / 59.2 / 59.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
33.1 / 33.1 / 36.2
33.1 / 36.2 / 36.2
36.2 / 36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 267 / 298
267 / 298 / 298
298 / 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
551.5
565.7
579.8
Reactive power reduction/saving
(4)
kVAr
101.7
99.4
97.1
Maximum Start Amps
A
786.8
801.0
815.1
Recommended Mains Fuse Size
A
670
670
670
Electronic Soft-start
Nominal Run Amps
A
613.4
625.5
637.6
Maximum Start Amps
A
729.5
741.6
753.7
Recommended Mains Fuse
A
670
670
670
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
551.5
565.7
579.8
Maximum Start Amps
A
667.6
681.8
695.9
Recommended Mains Fuse Size
A
670.0
670.0
670.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
35.0
Unit Nominal Run Amps
A
641.9
653.9
672.6
Recommended Mains Fuse Size
A
670
710
710
Motor Rating
kW
16.4
16.4
20.3
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
41.5
Unit Nominal Run Amps
A
648.4
660.4
679.0
Recommended Mains Fuse Size
A
670
710
710
Motor Rating
kW
20.3
20.3
23.9
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
33.2
Unit Nominal Run Amps
A
634.2
646.4
663.6
Recommended Mains Fuse Size
A
670
710
710
Motor Rating
kW
16.8
16.8
20.7
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
39.2
Unit Nominal Run Amps
A
639.1
651.3
668.3
Recommended Mains Fuse Size
A
670
710
710
Motor Rating
kW
20.7
20.7
24.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet