Introduction

Nomenclature

Introduction

The DeltaChill Free Cool chiller has been designed to provide the cooling load required whilst optimising energy

efficiency at all times and as such will take advantage of free cooling whenever available. If the free cooling available

cannot satisfy the required full cooling load, direct expansion cooling is used to supplement the output.

Specifiers Guide

Free Cooling Operation

In high ambients where free cooling is not available the fan

speed modulates in the conventional manner to maintain a

constant head pressure. Free cooling is initiated wherever the

outdoor ambient is 2°C less than the return water temperature.

The condensing temperature is constantly monitored and

intelligently kept within the compressor envelope to allow the

fans to run as fast as possible and therefore achieve the most

free-cooling without having a negative impact on compressor

integrity.

Free - cooling vs Mechanical cooling

System operated on 100% Free

Cooling (77% of Year)

System operated on

mechanical cooling only (23%

of Year)

Cooling

Load

Mechanical (Compressor) cooling

Free - Cooling

-7°C

0.5°C

12.5°C

Ambient Temp

DC

F

xxx

D

R-

07

x

X

Y

0

DC

DeltaChill

F

F = FreeCool Chiller, C = Air Cooled Chiller

xxx

Nominal Capacity (kW/10)

Number of Circuits

D

Dual Circuit

T

Triple Circuit

Noise Variant

R-

Regular Quiet

X-

Extra Quiet

07 - 22

Number of Fans

C - H

Evaporator Type

A - Y

A - Y

A - Y

Example

Document Navigation

The units have a unique number * (apart from the Nomenclature) for you to search each table of data.
For example Number “1” DCF046DR-07DXY0 is referenced in all tables, Performance, Mechanical, Electrical, Noise etc.

*This number is only used within this document. Please contact Airedale with the full nomenclature for product information.

In ambients where the free cooling coil is capable of satisfying the full cooling demand, the condenser fans are

modulated to provide the desired duty. The condenser fans are capable of being modulated between 25-100% of airflow

to maintain the supply water temperature.

During periods where the condenser fan speed has been reduced to a minimum, the supply water temperature will then

be controlled by the 3 way valve.