Chillers

DeltaChill™ Air Cooled and FreeCool

Installation Data

Weights, Point Loadings & Centre of Gravity (C of G) DCF

(1) Point load numbering starts from the control panel end of the chiller. Illustration above is for a 8 mount configuration
(2) Point loads indicated are for standard unit only

2

1

L1

L2

L3

L4

R1

R2

R3

R4

= C of G

Point load

L1

L2

L3

L4

L5

L6

L7

R1

R2

R3

R4

R5

R6

R7

C of

G 1

C of

G 2

kg

mm

mm

1

DCF046DR-07DXY0

655

750

825

830

950

1050

1225

2485

2

DCF048DR-07DPY0

620

745

845

765

915

1040

1210

2550

3

DCF051DR-08DPV0

650

760

850

805

940

1050

1210

2515

4

DCF053DR-08DYY0

685

765

830

875

975

1060

1225

2440

5

DCF049DR-09DXY0

680

665

650

635

815

795

780

765

1195

2760

6

DCF051DR-09DPY0

655

655

650

650

765

765

760

755

1180

2825

7

DCF053DR-10DPV0

670

670

665

665

785

780

780

775

1180

2825

8

DCF055DR-09DYV0

680

665

650

635

830

805

790

770

1200

2755

9

DCF055DR-10DYY0

695

680

665

650

840

815

800

780

1195

2755

10 DCF058DR-10DVV0

700

685

670

650

855

830

815

790

1205

2750

11

DCF062DR-10FVW0

715

700

685

665

870

845

830

810

1200

2750

12 DCF065DR-10FWW0

720

700

685

665

875

855

835

810

1205

2745

13 DCF069TR-10GPPY

715

745

765

795

860

895

920

955

1195

2965

14 DCF051DR-11DXY0

795

765

735

695

915

880

845

800

1175

3205

15 DCF053DR-11DPY0

775

755

735

710

870

845

825

795

1160

3275

16 DCF055DR-12DPV0

800

775

745

710

900

870

835

800

1160

3230

17 DCF057DR-12DYY0

825

790

750

700

950

910

860

810

1175

3155

18 DCF058DR-11DYV0

800

770

735

700

930

895

855

810

1180

3195

19 DCF060DR-12DVV0

830

790

745

700

965

920

870

815

1180

3150

20 DCF065DR-12FVW0

855

815

765

710

985

935

880

815

1170

3125

21 DCF068DR-12FWW0

860

825

785

735

1020

975

930

870

1190

3170

22 DCF074TR-11GPYY

850

850

850

850

1040

1040

1040

1040

1205

3405

23 DCF079TR-12GYYY

900

880

860

835

1125

1100

1075

1045

1215

3290

24 DCF059DR-13DYV0

725

690

650

690

585

830

790

745

790

670

1170

3585

25 DCF062DR-14DVV0

740

700

665

700

595

850

810

765

810

685

1175

3580