Chillers deltachill™ air cooled and freecool, Te ch nic al, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 247: Dcc electrical data - extra quiet

Advertising
background image

247

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

ELECTRICAL DATA

149

150

151

Unit Data

DCC058DX-12DVW0

DCC061DX-12DWW0

DCC050DX-14EPV0

Nominal Run Amps

(1)

A

393.0

405.3

335.2

Maximum Start Amps

A

628.3

640.6

570.5

Recommended Mains Fuse Size

A

450

450

355

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

12

12

14

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

12

12

14

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 59.2

59.2 / 59.2

59.2 / 55.2

Quantity

3 + 3

3 + 3

2 + 3

Motor Rating

kW

33.1 / 36.2

36.2 / 36.2

36.2 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

267 / 298

298 / 298

298 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

359.1

373.2

304.6

Reactive power reduction/saving

(4)

kVAr

57.5

55.2

51.4

Maximum Start Amps

A

594.4

608.5

539.9

Recommended Mains Fuse Size

A

450

450

355

Electronic Soft-start
Nominal Run Amps

A

393.0

405.3

335.2

Maximum Start Amps

A

509.1

521.4

451.3

Recommended Mains Fuse

A

450

450

355

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

359.1

373.2

304.6

Maximum Start Amps

A

475.2

489.3

420.7

Recommended Mains Fuse Size

A

450

450

355

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

8.9

Unit Nominal Run Amps

A

404.1

416.3

343.9

Recommended Mains Fuse Size

A

450

450

400

Motor Rating

kW

6.2

6.2

4.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

404.1

416.3

346.3

Recommended Mains Fuse Size

A

450

450

400

Motor Rating

kW

6.1

6.1

6.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

10.2

10.2

7.3

Unit Nominal Run Amps

A

401.0

413.3

340.9

Recommended Mains Fuse Size

A

450

450

400

Motor Rating

kW

6.4

6.4

4.5

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

10.1

10.1

10.1

Unit Nominal Run Amps

A

400.9

413.2

343.1

Recommended Mains Fuse Size

A

450

450

400

Motor Rating

kW

6.3

6.3

6.3

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Extra Quiet