Chillers deltachill™ air cooled and freecool, Te ch nic al, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 247: Dcc electrical data - extra quiet
![background image](/manuals/370937/247/background.png)
247
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
A
ir C
oo
led
ELECTRICAL DATA
149
150
151
Unit Data
DCC058DX-12DVW0
DCC061DX-12DWW0
DCC050DX-14EPV0
Nominal Run Amps
(1)
A
393.0
405.3
335.2
Maximum Start Amps
A
628.3
640.6
570.5
Recommended Mains Fuse Size
A
450
450
355
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
12
12
14
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
12
12
14
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 59.2
59.2 / 59.2
59.2 / 55.2
Quantity
3 + 3
3 + 3
2 + 3
Motor Rating
kW
33.1 / 36.2
36.2 / 36.2
36.2 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 298
298 / 298
298 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
359.1
373.2
304.6
Reactive power reduction/saving
(4)
kVAr
57.5
55.2
51.4
Maximum Start Amps
A
594.4
608.5
539.9
Recommended Mains Fuse Size
A
450
450
355
Electronic Soft-start
Nominal Run Amps
A
393.0
405.3
335.2
Maximum Start Amps
A
509.1
521.4
451.3
Recommended Mains Fuse
A
450
450
355
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
359.1
373.2
304.6
Maximum Start Amps
A
475.2
489.3
420.7
Recommended Mains Fuse Size
A
450
450
355
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
8.9
Unit Nominal Run Amps
A
404.1
416.3
343.9
Recommended Mains Fuse Size
A
450
450
400
Motor Rating
kW
6.2
6.2
4.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
404.1
416.3
346.3
Recommended Mains Fuse Size
A
450
450
400
Motor Rating
kW
6.1
6.1
6.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.2
10.2
7.3
Unit Nominal Run Amps
A
401.0
413.3
340.9
Recommended Mains Fuse Size
A
450
450
400
Motor Rating
kW
6.4
6.4
4.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
10.1
10.1
10.1
Unit Nominal Run Amps
A
400.9
413.2
343.1
Recommended Mains Fuse Size
A
450
450
400
Motor Rating
kW
6.3
6.3
6.3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Extra Quiet