Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 141: Dcf electrical data - regular quiet
141
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
ELECTRICAL DATA
34
35
36
Unit Data
DCF085TR-16HYYV
DCF090TR-15HVVV
DCF092TR-15HVVW
Nominal Run Amps
(1)
A
542.8
589.0
601.1
Maximum Start Amps
A
771.2
797.4
836.4
Recommended Mains Fuse Size
A
630
630
630
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
16
15
15
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
16
15
15
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
Quantity
16
15
15
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 47.5 / 55.2
55.2 / 55.2 / 55.2
55.2 / 55.2 / 59.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
29.6 / 29.6 / 33.1
33.1 / 33.1 / 33.1
33.1 / 33.1 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 287 / 267
267 / 267 / 267
267 / 267 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
496.7
528.3
542.4
Reactive power reduction/saving
(4)
kVAr
78.5
99.3
97.0
Maximum Start Amps
A
725.1
736.7
777.7
Recommended Mains Fuse Size
A
630
630
630
Electronic Soft-start
Nominal Run Amps
A
542.8
589.0
601.1
Maximum Start Amps
A
656.4
690.6
717.2
Recommended Mains Fuse
A
630
630
630
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
496.7
528.3
542.4
Maximum Start Amps
A
610.3
629.9
658.5
Recommended Mains Fuse Size
A
630.0
630.0
630.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
571.2
617.5
629.5
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
16.4
16.4
16.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
35.0
Unit Nominal Run Amps
A
577.7
624.0
636.0
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
20.3
20.3
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
564.0
609.8
621.9
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
16.8
16.8
16.8
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
33.2
Unit Nominal Run Amps
A
569.0
614.7
626.9
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
20.7
20.7
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet