Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 141: Dcf electrical data - regular quiet

Advertising
background image

141

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

ELECTRICAL DATA

34

35

36

Unit Data

DCF085TR-16HYYV

DCF090TR-15HVVV

DCF092TR-15HVVW

Nominal Run Amps

(1)

A

542.8

589.0

601.1

Maximum Start Amps

A

771.2

797.4

836.4

Recommended Mains Fuse Size

A

630

630

630

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

16

15

15

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

16

15

15

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)
Quantity

16

15

15

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 47.5 / 55.2

55.2 / 55.2 / 55.2

55.2 / 55.2 / 59.2

Quantity

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

Motor Rating

kW

29.6 / 29.6 / 33.1

33.1 / 33.1 / 33.1

33.1 / 33.1 / 36.2

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 287 / 267

267 / 267 / 267

267 / 267 / 298

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

496.7

528.3

542.4

Reactive power reduction/saving

(4)

kVAr

78.5

99.3

97.0

Maximum Start Amps

A

725.1

736.7

777.7

Recommended Mains Fuse Size

A

630

630

630

Electronic Soft-start
Nominal Run Amps

A

542.8

589.0

601.1

Maximum Start Amps

A

656.4

690.6

717.2

Recommended Mains Fuse

A

630

630

630

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

496.7

528.3

542.4

Maximum Start Amps

A

610.3

629.9

658.5

Recommended Mains Fuse Size

A

630.0

630.0

630.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

571.2

617.5

629.5

Recommended Mains Fuse Size

A

630

670

670

Motor Rating

kW

16.4

16.4

16.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

35.0

35.0

Unit Nominal Run Amps

A

577.7

624.0

636.0

Recommended Mains Fuse Size

A

630

670

670

Motor Rating

kW

20.3

20.3

20.3

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

564.0

609.8

621.9

Recommended Mains Fuse Size

A

630

670

670

Motor Rating

kW

16.8

16.8

16.8

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

33.2

33.2

Unit Nominal Run Amps

A

569.0

614.7

626.9

Recommended Mains Fuse Size

A

630

670

670

Motor Rating

kW

20.7

20.7

20.7

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet