DCC Electrical Data - Extra Quiet

ELECTRICAL DATA

146

147

148

Unit Data

DCC051DX-12EYY0

DCC053DX-11DYV0

DCC056DX-12DVV0

Nominal Run Amps

(1)

A

331.2

353.4

380.9

Maximum Start Amps

A

567.8

581.8

589.3

Recommended Mains Fuse Size

A

355

400

400

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

12

11

12

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

12

11

12

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 47.5

47.5 / 55.2

55.2 / 55.2

Quantity

3 + 3

3 + 3

3 + 3

Motor Rating

kW

29.6 / 29.6

29.6 / 33.1

33.1 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 287

287 / 267

267 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

310.3

325.7

345.0

Reactive power reduction/saving

(4)

kVAr

37.4

47.9

59.8

Maximum Start Amps

A

546.9

554.1

553.4

Recommended Mains Fuse Size

A

355

400

400

Electronic Soft-start
Nominal Run Amps

A

331.2

353.4

380.9

Maximum Start Amps

A

453.0

467.0

482.5

Recommended Mains Fuse

A

355

400

400

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

310.3

325.7

345.0

Maximum Start Amps

A

432.1

439.3

446.6

Recommended Mains Fuse Size

A

355

400

400

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

8.9

8.9

8.9

Unit Nominal Run Amps

A

339.7

362.0

389.5

Recommended Mains Fuse Size

A

355

400

450

Motor Rating

kW

4.4

4.4

4.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

342.2

364.5

392.0

Recommended Mains Fuse Size

A

400

400

450

Motor Rating

kW

6.1

6.1

6.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

7.3

7.3

7.3

Unit Nominal Run Amps

A

337.0

359.1

386.5

Recommended Mains Fuse Size

A

355

400

450

Motor Rating

kW

4.5

4.5

4.5

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

10.1

10.1

10.1

Unit Nominal Run Amps

A

339.3

361.4

388.7

Recommended Mains Fuse Size

A

400

400

450

Motor Rating

kW

6.3

6.3

6.3

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold