DCC Electrical Data - Extra Quiet
ELECTRICAL DATA
146
147
148
Unit Data
DCC051DX-12EYY0
DCC053DX-11DYV0
DCC056DX-12DVV0
Nominal Run Amps
(1)
A
331.2
353.4
380.9
Maximum Start Amps
A
567.8
581.8
589.3
Recommended Mains Fuse Size
A
355
400
400
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
12
11
12
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
12
11
12
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 47.5
47.5 / 55.2
55.2 / 55.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
29.6 / 29.6
29.6 / 33.1
33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 287
287 / 267
267 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
310.3
325.7
345.0
Reactive power reduction/saving
(4)
kVAr
37.4
47.9
59.8
Maximum Start Amps
A
546.9
554.1
553.4
Recommended Mains Fuse Size
A
355
400
400
Electronic Soft-start
Nominal Run Amps
A
331.2
353.4
380.9
Maximum Start Amps
A
453.0
467.0
482.5
Recommended Mains Fuse
A
355
400
400
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
310.3
325.7
345.0
Maximum Start Amps
A
432.1
439.3
446.6
Recommended Mains Fuse Size
A
355
400
400
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
8.9
Unit Nominal Run Amps
A
339.7
362.0
389.5
Recommended Mains Fuse Size
A
355
400
450
Motor Rating
kW
4.4
4.4
4.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
342.2
364.5
392.0
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
6.1
6.1
6.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
7.3
7.3
7.3
Unit Nominal Run Amps
A
337.0
359.1
386.5
Recommended Mains Fuse Size
A
355
400
450
Motor Rating
kW
4.5
4.5
4.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
10.1
10.1
10.1
Unit Nominal Run Amps
A
339.3
361.4
388.7
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
6.3
6.3
6.3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold