ELECTRICAL DATA

61

62

63

Unit Data

DCF058DX-12DVV0

DCF062DX-12FVW0

DCF065DX-12FWW0

Nominal Run Amps

(1)

A

380.9

393.0

405.3

Maximum Start Amps

A

589.3

628.3

640.6

Recommended Mains Fuse Size

A

400

450

450

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

12

12

12

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

12

12

12

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 55.2

55.2 / 59.2

59.2 / 59.2

Quantity

3 + 3

3 + 3

3 + 3

Motor Rating

kW

33.1 / 33.1

33.1 / 36.2

36.2 / 36.2

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

267 / 267

267 / 298

298 / 298

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

345.0

359.1

373.2

Reactive power reduction/saving

(4)

kVAr

59.8

57.5

55.2

Maximum Start Amps

A

553.4

594.4

608.5

Recommended Mains Fuse Size

A

400

450

450

Electronic Soft-start
Nominal Run Amps

A

380.9

393.0

405.3

Maximum Start Amps

A

482.5

509.1

521.4

Recommended Mains Fuse

A

400

450

450

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

345.0

359.1

373.2

Maximum Start Amps

A

446.6

475.2

489.3

Recommended Mains Fuse Size

A

400

450

450

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

402.0

414.2

426.4

Recommended Mains Fuse Size

A

450

450

450

Motor Rating

kW

12.1

12.1

12.1

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

409.3

421.5

433.7

Recommended Mains Fuse Size

A

450

450

500

Motor Rating

kW

16.4

16.4

16.4

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

396.3

408.6

421.0

Recommended Mains Fuse Size

A

450

450

450

Motor Rating

kW

12.4

12.4

12.4

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

401.9

414.2

426.6

Recommended Mains Fuse Size

A

450

450

450

Motor Rating

kW

16.8

16.8

16.8

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data Extra Quiet