ELECTRICAL DATA
61
62
63
Unit Data
DCF058DX-12DVV0
DCF062DX-12FVW0
DCF065DX-12FWW0
Nominal Run Amps
(1)
A
380.9
393.0
405.3
Maximum Start Amps
A
589.3
628.3
640.6
Recommended Mains Fuse Size
A
400
450
450
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
12
12
12
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
12
12
12
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2
55.2 / 59.2
59.2 / 59.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
33.1 / 33.1
33.1 / 36.2
36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 267
267 / 298
298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
345.0
359.1
373.2
Reactive power reduction/saving
(4)
kVAr
59.8
57.5
55.2
Maximum Start Amps
A
553.4
594.4
608.5
Recommended Mains Fuse Size
A
400
450
450
Electronic Soft-start
Nominal Run Amps
A
380.9
393.0
405.3
Maximum Start Amps
A
482.5
509.1
521.4
Recommended Mains Fuse
A
400
450
450
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
345.0
359.1
373.2
Maximum Start Amps
A
446.6
475.2
489.3
Recommended Mains Fuse Size
A
400
450
450
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
402.0
414.2
426.4
Recommended Mains Fuse Size
A
450
450
450
Motor Rating
kW
12.1
12.1
12.1
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
409.3
421.5
433.7
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
16.4
16.4
16.4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
396.3
408.6
421.0
Recommended Mains Fuse Size
A
450
450
450
Motor Rating
kW
12.4
12.4
12.4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
401.9
414.2
426.6
Recommended Mains Fuse Size
A
450
450
450
Motor Rating
kW
16.8
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet