Chillers

DeltaChill™ Air Cooled and FreeCool

27

Chiller Technical Manual 7267818 V1.4.0_04_2014

Introduction

Alarm Handling

The controller logs and allows viewing of the last 100 conditions recorded in descending chronological order through the

keypad display.
The following conditions will be detected, triggering a visual display:

Common for both circuits (Multiple Circuit units):

Low Supply Temperature

Emergency Stop

Water Flow

Pump(s) status

Pump(s) remote start

Volt Free Contact Alarm Indication

Individual for each circuit:

Individual alarms will isolate the affected circuit only.

Compressor Trip

Low Suction Pressure for each circuit

High Liquid Pressure for each circuit

Low Pressure Switch

Compressor Overload

High Compressor Discharge Temperature

Optional Features

Networking

A Local Area Network (LAN) can be used to connect a number of chiller controllers to offer intercommunication and

sequence control. There is also the facility to allow the connection of either a computer or modem for local or remote

monitoring. For further details, please contact Airedale.

CAUTION

When adding to an existing network, please consult Airedale to ensure strategy compatibility.

Unit Remote ON/OFF

Disables/Enables the Chiller remotely.

Compressor Anti Cycle Control

Automatic via the Microprocessor.

Compressor Load Limit

Limits the condensing pressure by unloading above 35 Barg.
Limits the evaporating pressure by unloading at the minimum pressure set point, which is, adjustable depending on

system glycol content.

Pump(s) Remote ON/OFF

Disables/Enables the pump(s) remotely.

Remote Setback Temperature Set point Switch

A setback set point for supply water temperature can be selected to suit summer/winter conditions or night setback.