Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

Fre

eC

oo

l

ELECTRICAL DATA

4

5

6

Unit Data

DCF053DR-08DYY0

DCF049DR-09DXY0

DCF051DR-09DPY0

Nominal Run Amps

(1)

A

334.5

306.2

312.9

Maximum Start Amps

A

571.1

542.8

548.2

Recommended Mains Fuse Size

A

355

355

355

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

8

9

9

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

8

9

9

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)

2.6

2.6

2.6

Quantity

8

9

9

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 47.5

37.1 / 47.5

59.2 / 47.5

Quantity

3 + 3

3 + 3

2 + 3

Motor Rating

kW

29.6 / 29.6

23.5 / 29.6

36.2 / 29.6

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 287

210 / 287

298 / 287

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

311.5

285.8

287.6

Reactive power reduction/saving

(4)

kVAr

40.7

36.3

43.5

Maximum Start Amps

A

548.1

522.4

522.9

Recommended Mains Fuse Size

A

355

355

355

Electronic Soft-start
Nominal Run Amps

A

334.5

306.2

312.9

Maximum Start Amps

A

456.3

428.0

429.0

Recommended Mains Fuse

A

355

355

355

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

311.5

285.8

287.6

Maximum Start Amps

A

433.3

407.6

403.7

Recommended Mains Fuse Size

A

355.0

355.0

355.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

14.8

14.8

14.8

Unit Nominal Run Amps

A

349.2

320.9

327.7

Recommended Mains Fuse Size

A

400

355

355

Motor Rating

kW

8.4

8.4

8.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

21.2

21.2

Unit Nominal Run Amps

A

362.9

327.3

334.1

Recommended Mains Fuse Size

A

400

355

355

Motor Rating

kW

16.4

12.1

12.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

13.9

13.9

13.9

Unit Nominal Run Amps

A

345.6

317.3

323.9

Recommended Mains Fuse Size

A

400

355

355

Motor Rating

kW

8.6

8.6

8.6

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

19.8

19.8

Unit Nominal Run Amps

A

356.1

322.2

328.6

Recommended Mains Fuse Size

A

400

355

355

Motor Rating

kW

16.8

12.4

12.4

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet