Chillers deltachill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 131: Dcf electrical data - regular quiet
131
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
ELECTRICAL DATA
4
5
6
Unit Data
DCF053DR-08DYY0
DCF049DR-09DXY0
DCF051DR-09DPY0
Nominal Run Amps
(1)
A
334.5
306.2
312.9
Maximum Start Amps
A
571.1
542.8
548.2
Recommended Mains Fuse Size
A
355
355
355
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
8
9
9
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
8
9
9
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
2.6
2.6
2.6
Quantity
8
9
9
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 47.5
37.1 / 47.5
59.2 / 47.5
Quantity
3 + 3
3 + 3
2 + 3
Motor Rating
kW
29.6 / 29.6
23.5 / 29.6
36.2 / 29.6
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 287
210 / 287
298 / 287
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
311.5
285.8
287.6
Reactive power reduction/saving
(4)
kVAr
40.7
36.3
43.5
Maximum Start Amps
A
548.1
522.4
522.9
Recommended Mains Fuse Size
A
355
355
355
Electronic Soft-start
Nominal Run Amps
A
334.5
306.2
312.9
Maximum Start Amps
A
456.3
428.0
429.0
Recommended Mains Fuse
A
355
355
355
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
311.5
285.8
287.6
Maximum Start Amps
A
433.3
407.6
403.7
Recommended Mains Fuse Size
A
355.0
355.0
355.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
14.8
Unit Nominal Run Amps
A
349.2
320.9
327.7
Recommended Mains Fuse Size
A
400
355
355
Motor Rating
kW
8.4
8.4
8.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
21.2
21.2
Unit Nominal Run Amps
A
362.9
327.3
334.1
Recommended Mains Fuse Size
A
400
355
355
Motor Rating
kW
16.4
12.1
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
13.9
13.9
13.9
Unit Nominal Run Amps
A
345.6
317.3
323.9
Recommended Mains Fuse Size
A
400
355
355
Motor Rating
kW
8.6
8.6
8.6
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
19.8
19.8
Unit Nominal Run Amps
A
356.1
322.2
328.6
Recommended Mains Fuse Size
A
400
355
355
Motor Rating
kW
16.8
12.4
12.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet