Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf electrical data extra quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 158
158
Chiller Technical Manual 7267818 V1.4.0_04_2014
Chillers
DeltaChill™ Air Cooled and FreeCool
Te
ch
ni
ca
l
Fr
ee
C
oo
l
ELECTRICAL DATA
85
86
87
Unit Data
DCF092TX-18HVVW
DCF094TX-18HVWW
DCF096TX-18HWWW
Nominal Run Amps
(1)
A
583.4
595.6
607.9
Maximum Start Amps
A
818.7
830.9
843.2
Recommended Mains Fuse Size
A
630
630
630
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
18
18
18
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
18
18
18
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2 / 59.2
55.2 / 59.2 / 59.2
59.2 / 59.2 / 59.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
33.1 / 33.1 / 36.2
33.1 / 36.2 / 36.2
36.2 / 36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 267 / 298
267 / 298 / 298
298 / 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
531.6
545.7
559.8
Reactive power reduction/saving
(4)
kVAr
87.5
85.2
82.9
Maximum Start Amps
A
766.9
781.0
795.1
Recommended Mains Fuse Size
A
630
630
630
Electronic Soft-start
Nominal Run Amps
A
583.4
595.6
607.9
Maximum Start Amps
A
699.5
711.7
724.0
Recommended Mains Fuse
A
630
630
630
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
531.6
545.7
559.8
Maximum Start Amps
A
647.7
661.8
675.9
Recommended Mains Fuse Size
A
630
630
630
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
611.9
624.1
636.3
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
16.4
16.4
16.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
35.0
Unit Nominal Run Amps
A
618.4
630.6
642.8
Recommended Mains Fuse Size
A
670
670
670
Motor Rating
kW
20.3
20.3
20.3
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
604.5
616.8
629.2
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
16.8
16.8
16.8
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
33.2
Unit Nominal Run Amps
A
609.5
621.8
634.2
Recommended Mains Fuse Size
A
670
670
670
Motor Rating
kW
20.7
20.7
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet