Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf mechanical data extra quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 128

Advertising
background image

128

Chiller Technical Manual 7267818 V1.4.0_04_2014

Chillers

DeltaChill™ Air Cooled and FreeCool

Te

ch

ni

ca

l

Fr

ee

C

oo

l

94

95

96

97

DCF092TX-21HVVV

DCF095TX-21HVVW

DCF097TX-21HVWW

DCF099TX-21HWWW

FreeCooling

Y

Y

Y

Y

Enhance Capital Allowance

N

N

N

N

Number of Refrigeration Circuits

3

3

3

3

Cooling Duty - High Airflow EC Fans
Nominal Output - Mechanical

(1)

kW

N/A

N/A

N/A

N/A

Nominal Input - Mechanical

kW

N/A

N/A

N/A

N/A

EER

(2)

N/A

N/A

N/A

N/A

ESEER

N/A

N/A

N/A

N/A

SEER

N/A

N/A

N/A

N/A

Nominal Output - Free Cooling

kW

N/A

N/A

N/A

N/A

Ambient temperature for 100% Free Cooling

(5)

°C

N/A

N/A

N/A

N/A

Cooling Duty - EC Fans
Nominal Output - Mechanical

(1)

kW

920.1

947.0

974.0

993.6

Nominal Input - Mechanical

kW

283.8

296.2

308.7

320.4

EER

(2)

3.07

3.04

3.01

2.97

ESEER

4.60

4.58

4.55

4.47

SEER

4.43

4.41

4.38

4.31

Nominal Output - Free Cooling

kW

754.2

761.3

767.9

772.5

Ambient temperature for 100% Free Cooling

(5)

°C

0.3

-0.0

-0.3

-0.5

Cooling Duty - AC Fans
Nominal Output - Mechanical

(1)

kW

920.4

947.4

974.4

994.0

Nominal Input - Mechanical

kW

291.7

304.2

316.6

328.3

EER

(2)

2.99

2.96

2.93

2.89

ESEER

4.18

4.17

4.15

4.10

SEER

4.05

4.04

4.02

3.97

Nominal Output - Free Cooling

kW

755.4

762.5

769.1

773.7

Ambient temperature for 100% Free Cooling

(5)

°C

0.3

-0.0

-0.3

-0.5

Capacity Steps

%

10-25-35-45-60-

70-80-90-100

10-25-35-45-55-

70-80-90-100

10-25-35-45-60-

70-80-90-100

10-25-35-45-60-

70-80-90-100

Minimum Turndown Ratio

0.12

0.11

0.11

0.12

Dimensions (H x W x L)

mm

2682 x 2200 x 12770

2682 x 2200 x 12770

2682 x 2200 x 12770

2682 x 2200 x 12770

Weight
Machine

(3)

kg

9690

9715

9745

9775

Operating

kg

11585

11615

11645

11670

Water Volume (Total Internal)

l

1895

1900

1900

1895

Maximum Waterflow

l/s

63.4

63.4

63.4

83.7

Minimum Waterflow

l/s

24.0

24.0

24.0

32.1

Face Area (Total)

2.38

2.38

2.38

2.38

Nominal Airflow - High Airflow EC Fans

m³/s

N/A

N/A

N/A

N/A

Nominal Airflow - EC Fans

m³/s

83.9

83.9

83.9

83.9

Nominal Airflow - AC Fans

m³/s

84.2

84.2

84.2

84.2

Quantity

21

21

21

21

Maximum Speed - High Airflow EC Fans

rpm

N/A

N/A

N/A

N/A

Maximum Speed - EC Fans

rpm

725

725

725

725

Maximum Speed - AC Fans

rpm

714

714

714

714

Compressor

Trio + Trio + Trio

Trio + Trio + Trio

Trio + Trio + Trio

Trio + Trio + Trio

Quantity of Compressors

9

9

9

9

Oil Charge Volume (Total)

l

3 x 5.3 + 3 x 5.3 + 3 x 5.33 x 5.3 + 3 x 5.3 + 3 x 5.33 x 5.3 + 3 x 5.3 + 3 x 5.33 x 5.3 + 3 x 5.3 + 3 x 5.3

Refrigeration
Charge (Total)

kg

45 + 44 + 48

45 + 44 + 48

45 + 44 + 48

45 + 44 + 48

Water Inlet / Outlet - Unit

DN150

DN150

DN150

DN150

Water Drain / Bleed - Evap

inch

0.5

0.5

0.5

0.5

Water System
Minimum System Water Volume

(4)

l

7971

8188

8405

8715

Maximum System Operating Pressure

Bar

10

10

10

10

(1)

Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol

(2)

EER = DX Cooling Output / (Compressor input power + Fan Input Power),

(3)

Based on standard unit without options, operating weight includes refrigerant charge and water volume.

For unit weights with waterside options fitted please refer to Airedale.

(4)

For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations

(5)

Ambient temperature that full Freecool capacity can be achieved

DCF Mechanical Data Extra Quiet

Advertising
This manual is related to the following products: