Chillers deltachill™ air cooled and freecool, Te ch nic al, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 191: Dcc performance data ec fans

Advertising
background image

191

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

Ambient (°C)

Model

Supply Temp

°C

25°C

30°C

35°C

40°C

Output

Input

Output

Input

Output

Input

Output

Input

kW

kW

kW

kW

kW

kW

kW

kW

128

DCC088TR-15GVWW

5

946.1

256.6

900.9

282.4

846.4

311.0

785.9

343.1

6

974.4

258.6

927.4

284.3

871.2

312.9

809.1

345.1

7

1003.2

260.6

954.4

286.2

896.4

314.9

832.7

347.0

8

1032.3

262.7

981.7

288.2

921.9

316.9

856.6

349.1

9

1061.8

264.7

1009.3

290.2

947.7

318.9

880.8

351.1

10

1091.6

266.7

1037.1

292.2

973.8

321.0

905.4

353.2

129

DCC091TR-15GWWW

5

977.3

267.4

929.9

293.5

871.9

322.3

808.9

355.0

6

1006.3

269.5

956.7

295.5

897.2

324.4

832.5

357.1

7

1035.7

271.7

984.0

297.6

922.8

326.6

856.4

359.3

8

1065.6

273.9

1011.5

299.7

948.7

328.8

880.6

361.5

9

1095.7

276.1

1039.3

301.8

974.9

331.0

905.3

363.7

10

1126.1

278.3

1067.4

303.9

1001.5

333.3

930.2

366.0

130

DCC074TR-17GPYY

5

764.7

188.9

729.3

208.9

689.7

231.8

646.2

257.8

6

787.8

190.2

751.6

210.2

710.4

233.0

666.0

259.0

7

811.1

191.4

774.2

211.5

732.4

234.4

686.6

260.4

8

834.8

192.7

797.1

212.8

754.7

235.9

707.6

261.8

9

858.8

194.0

820.4

214.2

776.5

237.1

729.0

263.3

10

882.9

195.3

843.9

215.5

799.0

238.5

750.7

264.8

131

DCC079TR-18GYYY

5

822.2

201.7

783.8

223.2

740.0

247.6

693.7

275.8

6

847.4

203.0

808.0

224.6

764.1

249.3

715.7

277.3

7

872.9

204.4

832.6

226.0

787.6

250.7

738.1

278.8

8

898.6

205.7

857.5

227.4

810.8

252.0

761.0

280.3

9

924.8

207.1

882.8

228.8

835.2

253.5

784.2

281.8

10

951.3

208.6

908.5

230.3

859.9

255.0

807.8

283.3

132

DCC082TR-17GYVV

5

862.0

220.4

822.1

243.9

777.5

271.0

728.9

302.0

6

887.8

221.7

847.3

245.4

801.6

272.6

751.7

303.5

7

914.2

223.2

872.3

246.8

826.1

274.1

774.8

305.1

8

941.2

224.7

898.2

248.3

851.0

275.8

798.2

306.6

9

968.0

226.2

924.9

250.0

876.2

277.4

822.1

308.2

10

995.3

227.7

951.1

251.5

901.8

279.0

846.4

309.8

133

DCC085TR-18GVVV

5

887.4

226.1

846.6

250.4

800.6

278.3

750.8

310.4

6

914.1

227.5

872.4

251.9

825.4

279.8

774.3

312.0

7

941.1

228.9

897.8

253.2

850.5

281.4

798.3

313.6

8

968.5

230.4

924.4

254.7

876.1

283.0

822.7

315.3

9

996.2

231.8

951.9

256.4

902.0

284.6

847.5

316.9

10

1024.1

233.3

978.6

257.8

928.2

286.3

872.7

318.6

1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water ∆T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x ∆T)

6

For conditions outside of those quoted please refer to Airedale.

DCC Performance Data EC Fans

Advertising
This manual is related to the following products: