Chillers deltachill™ air cooled and freecool, Te ch ni ca l fr ee c oo l, Dcf electrical data extra quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 160

Advertising
background image

160

Chiller Technical Manual 7267818 V1.4.0_04_2014

Chillers

DeltaChill™ Air Cooled and FreeCool

Te

ch

ni

ca

l

Fr

ee

C

oo

l

ELECTRICAL DATA

91

92

93

Unit Data

DCF088TX-20HYVV

DCF084TX-21GYYY

DCF087TX-22HYYV

Nominal Run Amps

(1)

A

551.1

504.0

531.1

Maximum Start Amps

A

779.5

740.6

759.5

Recommended Mains Fuse Size

A

630

560

560

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

20

21

22

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

20

21

22

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 55.2 / 55.2

47.5 / 47.5 / 47.5

47.5 / 47.5 / 55.2

Quantity

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

Motor Rating

kW

29.6 / 33.1 / 33.1

29.6 / 29.6 / 29.6

29.6 / 29.6 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 267 / 267

287 / 287 / 287

287 / 287 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

504.0

471.3

490.5

Reactive power reduction/saving

(4)

kVAr

80.1

58.4

70.4

Maximum Start Amps

A

732.4

707.9

718.9

Recommended Mains Fuse Size

A

630

560

560

Electronic Soft-start
Nominal Run Amps

A

551.1

504.0

531.1

Maximum Start Amps

A

664.7

625.8

644.7

Recommended Mains Fuse

A

630

560

560

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

504.0

471.3

490.5

Maximum Start Amps

A

617.6

593.1

604.1

Recommended Mains Fuse Size

A

630

560

560

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

579.5

532.3

559.5

Recommended Mains Fuse Size

A

630

560

630

Motor Rating

kW

16.4

16.4

16.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

35.0

35.0

Unit Nominal Run Amps

A

586.0

538.8

566.0

Recommended Mains Fuse Size

A

630

560

630

Motor Rating

kW

20.3

20.3

20.3

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

572.3

525.6

552.4

Recommended Mains Fuse Size

A

630

560

630

Motor Rating

kW

16.8

16.8

16.8

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

33.2

33.2

Unit Nominal Run Amps

A

577.2

530.7

557.5

Recommended Mains Fuse Size

A

630

560

630

Motor Rating

kW

20.7

20.7

20.7

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data Extra Quiet