ELECTRICAL DATA
91
92
93
Unit Data
DCF088TX-20HYVV
DCF084TX-21GYYY
DCF087TX-22HYYV
Nominal Run Amps
(1)
A
551.1
504.0
531.1
Maximum Start Amps
A
779.5
740.6
759.5
Recommended Mains Fuse Size
A
630
560
560
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
20
21
22
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
20
21
22
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 55.2 / 55.2
47.5 / 47.5 / 47.5
47.5 / 47.5 / 55.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
29.6 / 33.1 / 33.1
29.6 / 29.6 / 29.6
29.6 / 29.6 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 267 / 267
287 / 287 / 287
287 / 287 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
504.0
471.3
490.5
Reactive power reduction/saving
(4)
kVAr
80.1
58.4
70.4
Maximum Start Amps
A
732.4
707.9
718.9
Recommended Mains Fuse Size
A
630
560
560
Electronic Soft-start
Nominal Run Amps
A
551.1
504.0
531.1
Maximum Start Amps
A
664.7
625.8
644.7
Recommended Mains Fuse
A
630
560
560
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
504.0
471.3
490.5
Maximum Start Amps
A
617.6
593.1
604.1
Recommended Mains Fuse Size
A
630
560
560
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
579.5
532.3
559.5
Recommended Mains Fuse Size
A
630
560
630
Motor Rating
kW
16.4
16.4
16.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
35.0
Unit Nominal Run Amps
A
586.0
538.8
566.0
Recommended Mains Fuse Size
A
630
560
630
Motor Rating
kW
20.3
20.3
20.3
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
572.3
525.6
552.4
Recommended Mains Fuse Size
A
630
560
630
Motor Rating
kW
16.8
16.8
16.8
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
33.2
Unit Nominal Run Amps
A
577.2
530.7
557.5
Recommended Mains Fuse Size
A
630
560
630
Motor Rating
kW
20.7
20.7
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet