ELECTRICAL DATA

143

144

145

Unit Data

DCC048DX-10EPV0

DCC049DX-10EYY0

DCC049DX-12EPV0

Nominal Run Amps

(1)

A

325.5

326.4

330.4

Maximum Start Amps

A

560.8

563.0

565.7

Recommended Mains Fuse Size

A

355

355

355

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

10

10

12

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

10

10

12

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 55.2

47.5 / 47.5

59.2 / 55.2

Quantity

2 + 3

3 + 3

2 + 3

Motor Rating

kW

36.2 / 33.1

29.6 / 29.6

36.2 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 267

287 / 287

298 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

296.9

306.5

300.7

Reactive power reduction/saving

(4)

kVAr

48.3

35.9

49.9

Maximum Start Amps

A

532.2

543.1

536.0

Recommended Mains Fuse Size

A

355

355

355

Electronic Soft-start
Nominal Run Amps

A

325.5

326.4

330.4

Maximum Start Amps

A

441.6

448.2

446.5

Recommended Mains Fuse

A

355

355

355

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

296.9

306.5

300.7

Maximum Start Amps

A

413.0

428.3

416.8

Recommended Mains Fuse Size

A

355

355

355

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

8.9

8.9

8.9

Unit Nominal Run Amps

A

334.1

334.8

339.0

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

4.4

4.4

4.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

336.6

337.4

341.5

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

6.1

6.1

6.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

7.3

7.3

7.3

Unit Nominal Run Amps

A

331.2

332.2

336.0

Recommended Mains Fuse Size

A

355

355

355

Motor Rating

kW

4.5

4.5

4.5

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

10.1

10.1

10.1

Unit Nominal Run Amps

A

333.4

334.5

338.3

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

6.3

6.3

6.3

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Extra Quiet