ELECTRICAL DATA
10
11
12
Unit Data
DCF058DR-10DVV0
DCF062DR-10FVW0
DCF065DR-10FWW0
Nominal Run Amps
(1)
A
392.7
404.7
416.9
Maximum Start Amps
A
601.1
640.0
652.2
Recommended Mains Fuse Size
A
450
450
450
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
0.0
0
0
Quantity
10
10
10
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
10
10
10
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
Quantity
10
10
10
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2
55.2 / 59.2
59.2 / 59.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
33.1 / 33.1
33.1 / 36.2
36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 267
267 / 298
298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
352.2
366.3
380.4
Reactive power reduction/saving
(4)
kVAr
66.2
63.9
61.6
Maximum Start Amps
A
560.6
601.6
615.7
Recommended Mains Fuse Size
A
450
450
450
Electronic Soft-start
Nominal Run Amps
A
392.7
404.7
416.9
Maximum Start Amps
A
494.3
520.8
533.0
Recommended Mains Fuse
A
450
450
450
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
352.2
366.3
380.4
Maximum Start Amps
A
453.8
482.4
496.5
Recommended Mains Fuse Size
A
450.0
450.0
450.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
28.5
Unit Nominal Run Amps
A
413.8
425.9
445.3
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
12.1
12.1
16.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
35.0
Unit Nominal Run Amps
A
421.2
433.2
451.8
Recommended Mains Fuse Size
A
450
500
500
Motor Rating
kW
16.4
16.4
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
26.9
Unit Nominal Run Amps
A
408.0
420.2
438.0
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
12.4
12.4
16.8
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
33.2
Unit Nominal Run Amps
A
413.5
425.7
443.0
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
16.8
16.8
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet