ELECTRICAL DATA

179

180

181

182

Unit Data

DCC085TX-21GVVV DCC088TX-21GVVW DCC091TX-21GVWW DCC094TX-21GWWW

Nominal Run Amps

(1)

A

578.6

590.8

602.9

615.2

Maximum Start Amps

A

787.0

826.1

838.2

850.5

Recommended Mains Fuse Size

A

630

630

630

670

Evaporator
Immersion Heater Rating

W

250

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

21

21

21

21

Full Load Amps

A

2.5

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

1.27

Condenser Fan - Per Fan (EC)
Quantity

21

21

21

21

Full Load Amps

A

3.9

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

2.56

Compressor - Per Compressor
Nominal Run Amps

A

55.2 / 55.2 / 55.2

55.2 / 55.2 / 59.2

55.2 / 59.2 / 59.2

59.2 / 59.2 / 59.2

Quantity

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

Motor Rating

kW

33.1 / 33.1 / 33.1

33.1 / 33.1 / 36.2

33.1 / 36.2 / 36.2

36.2 / 36.2 / 36.2

Sump Heater Rating

W

140

140

140

140

Start Amps

(2)

A

267 / 267 / 267

267 / 267 / 298

267 / 298 / 298

298 / 298 / 298

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

523.2

537.3

551.5

565.6

Reactive power reduction/saving

(4)

kVAr

92.0

89.7

87.5

85.2

Maximum Start Amps

A

731.6

772.6

786.8

800.9

Recommended Mains Fuse Size

A

630

630

630

670

Electronic Soft-start
Nominal Run Amps

A

578.6

590.8

602.9

615.17

Maximum Start Amps

A

680.2

706.9

719.0

731.27

Recommended Mains Fuse

A

630

630

630

670

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

523.2

537.3

551.5

565.61

Maximum Start Amps

A

624.8

653.4

667.6

681.71

Recommended Mains Fuse Size

A

630

630

630

670

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

15.2

15.2

Unit Nominal Run Amps

A

589.8

601.9

618.0

630.22

Recommended Mains Fuse Size

A

630

630

670

670

Motor Rating

kW

6.2

6.2

8.4

8.38

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

21.2

Unit Nominal Run Amps

A

599.8

611.9

624.1

636.3

Recommended Mains Fuse Size

A

630

630

670

670

Motor Rating

kW

12.1

12.1

12.1

12.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

10.2

10.2

13.9

13.9

Unit Nominal Run Amps

A

586.5

598.7

613.8

626.1

Recommended Mains Fuse Size

A

630

630

670

670

Motor Rating

kW

6.4

6.4

8.6

8.6

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

19.8

Unit Nominal Run Amps

A

594.0

606.3

618.5

630.8

Recommended Mains Fuse Size

A

630

630

670

670

Motor Rating

kW

12.4

12.4

12.4

12.4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Extra Quiet