Chillers deltachill™ air cooled and freecool, Te ch nic al, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 235: Dcc electrical data - regular quiet

Advertising
background image

235

Chiller Technical Manual 7267818 V1.4.0_04_2014

Te

ch

nic

al

Chillers

DeltaChill™ Air Cooled and FreeCool

A

ir C

oo

led

113

114

115

Unit Data

DCC069TR-11GPYY

DCC074TR-12GYYY

DCC056DR-13DYV0

Nominal Run Amps

(1)

A

472.0

501.7

379.8

Maximum Start Amps

A

707.3

738.3

608.2

Recommended Mains Fuse Size

A

500

560

400

Evaporator
Immersion Heater Rating

W

250

250

170

Condenser Fan - Per Fan (AC)
Quantity

11

12

13

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

11

12

13

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

59.2 / 47.5 / 47.5

47.5 / 47.5 / 47.5

47.5 / 55.2

Quantity

2 + 3 + 3

3 + 3 + 3

3 + 3

Motor Rating

kW

36.2 / 29.6 / 29.6

29.6 / 29.6 / 29.6

29.6 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

298 / 287 / 287

287 / 287 / 287

287 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

437.3

467.2

344.0

Reactive power reduction/saving

(4)

kVAr

60.7

61.0

59.7

Maximum Start Amps

A

672.6

703.8

572.4

Recommended Mains Fuse Size

A

500

560

400

Electronic Soft-start
Nominal Run Amps

A

472.0

501.7

379.8

Maximum Start Amps

A

588.1

623.5

493.4

Recommended Mains Fuse

A

500

560

400

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

437.3

467.2

344.0

Maximum Start Amps

A

553.4

589.0

457.6

Recommended Mains Fuse Size

A

500

560

400

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

11.2

11.2

8.9

Unit Nominal Run Amps

A

483.1

512.8

388.4

Recommended Mains Fuse Size

A

560

560

450

Motor Rating

kW

6.2

6.2

4.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

11.2

Unit Nominal Run Amps

A

493.1

522.8

390.9

Recommended Mains Fuse Size

A

560

560

450

Motor Rating

kW

12.1

12.1

6.1

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

10.2

10.2

7.3

Unit Nominal Run Amps

A

480.1

509.9

385.4

Recommended Mains Fuse Size

A

560

560

450

Motor Rating

kW

6.4

6.4

4.5

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

10.1

Unit Nominal Run Amps

A

487.8

517.6

387.6

Recommended Mains Fuse Size

A

560

560

450

Motor Rating

kW

12.4

12.4

6.3

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold

DCC Electrical Data - Regular Quiet

Advertising
This manual is related to the following products: