Ambient (°C)

Model

Supply Temp

°C

25°C

30°C

35°C

40°C

Output

Input

Output

Input

Output

Input

Output

Input

kW

kW

kW

kW

kW

kW

kW

kW

110

DCC058DR-12DVV0

5

607.1

155.2

576.9

170.2

543.1

187.9

506.2

208.3

6

625.0

156.0

594.1

171.1

559.4

188.8

521.5

209.3

7

643.2

156.8

611.5

171.9

575.9

189.7

537.1

210.3

8

661.6

157.6

629.1

172.8

592.6

190.7

552.9

211.3

9

680.2

158.4

646.9

173.7

609.6

191.7

568.9

212.3

10

699.0

159.3

664.9

174.6

626.7

192.6

585.1

213.3

111

DCC060DR-12DVW0

5

634.0

164.8

602.1

180.4

566.3

198.7

527.1

219.7

6

652.4

165.7

619.7

181.4

583.0

199.8

542.8

220.8

7

671.1

166.6

637.6

182.5

599.9

200.9

558.7

222.0

8

690.0

167.6

655.7

183.5

617.1

202.1

574.8

223.1

9

709.0

168.6

673.9

184.6

634.4

203.2

591.2

224.3

10

728.2

169.6

692.4

185.7

651.9

204.4

607.8

225.6

112

DCC063DR-12DWW0

5

672.8

174.9

638.0

191.2

599.0

210.2

556.5

231.7

6

692.3

176.1

656.5

192.5

616.5

211.5

572.8

233.0

7

711.9

177.2

675.3

193.7

634.1

212.8

589.3

234.4

8

731.8

178.4

694.2

195.0

652.1

214.1

606.1

235.7

9

751.9

179.6

713.4

196.3

670.2

215.5

623.1

237.2

10

772.1

180.8

732.7

197.6

688.5

216.9

640.3

238.6

113

DCC069TR-11GPYY

5

732.4

207.0

692.1

227.7

647.6

251.7

599.8

278.5

6

753.5

208.6

712.0

229.4

666.3

253.4

617.2

280.3

7

774.8

210.1

732.2

231.1

685.2

255.2

634.8

282.1

8

796.3

211.8

752.5

232.8

704.4

257.0

652.7

283.9

9

818.0

213.4

773.1

234.6

723.7

258.8

670.9

285.8

10

839.9

215.1

793.9

236.4

743.3

260.7

689.3

287.7

114

DCC074TR-12GYYY

5

790.4

219.8

746.9

242.1

699.1

267.8

647.9

296.6

6

813.5

221.4

768.7

243.8

719.6

269.6

666.9

298.5

7

836.8

223.1

790.8

245.5

740.3

271.4

686.3

300.3

8

860.4

224.7

813.1

247.3

761.3

273.2

706.0

302.2

9

884.2

226.5

835.7

249.1

782.6

275.2

725.9

304.2

10

908.3

228.2

858.6

251.0

804.1

277.1

746.1

306.2

115

DCC056DR-13DYV0

5

582.4

146.7

554.6

160.5

523.4

176.8

489.0

195.6

6

599.8

147.4

571.3

161.2

539.2

177.5

503.9

196.4

7

617.3

148.0

588.2

161.9

555.3

178.3

519.1

197.2

8

635.0

148.7

605.2

162.7

571.6

179.1

534.5

198.1

9

652.9

149.5

622.5

163.4

588.0

179.9

550.2

198.9

10

671.0

150.2

639.9

164.2

604.7

180.7

566.0

199.8

1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water ∆T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x ∆T)

6

For conditions outside of those quoted please refer to Airedale.

DCC Performance Data AC Fans