41
Chiller Technical Manual 7267818 V1.4.0_04_2014
In
sta
lla
tio
n
Chillers
DeltaChill™Air Cooled and FreeCool
Installation Data
Unit Lifting
•
Employ lifting specialists
•
Local codes and regulations relating to the lifting of this type of equipment should be observed
•
Use the appropriate spreader bars/lifting slings (provided by others) with the eye bolts/lugs provided.
•
Attach individual lifting chains to each of the lifting eye bolts/lifting lugs provided; each individual chain must be
capable of lifting the whole unit
•
Lifting Eye size is 40mm.
Lifting Dimensions
C
A1
Dimension (mm)
A1 (Min) A2 (Min)
B
C
7 / 8 Fan Unit
4000
N/A
N/A
3680
9 / 10 Fan Unit
5000
N/A
N/A
4415
11 / 12 Fan Unit
3500
3000
2340
3145
13 / 14 Fan Unit
4500
3000
2340
4077
15 / 16 Fan Unit
5000
3000
2800
4750
17 / 18 Fan Unit
6000
3000
2950
5730
19 / 20 Fan Unit
7000
4000
3150
6660
21 / 22 Fan Unit
7000
5000
4000
6930
IMPORTANT
Do not use 1 chain between 2 lifting points to avoid load shift.
Only use lifting points provided.
Chains/slings MUST NOT interfere with the casing or fan assembly to avoid damage.
Lift the unit slowly and evenly.
If the unit is dropped, it should immediately be checked for damage and reported to Airedale.