ELECTRICAL DATA
49
50
51
Unit Data
DCF098TR-21HVVW
DCF101TR-21HVWW
DCF103TR-21HWWW
Nominal Run Amps
(1)
A
625.8
637.8
649.9
Maximum Start Amps
A
861.1
873.1
885.2
Recommended Mains Fuse Size
A
670
670
710
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
21
21
21
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
21
21
21
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
2.6
2.6
2.6
Quantity
21
21
21
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2 / 59.2
55.2 / 59.2 / 59.2
59.2 / 59.2 / 59.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
33.1 / 33.1 / 36.2
33.1 / 36.2 / 36.2
36.2 / 36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
267 / 267 / 298
267 / 298 / 298
298 / 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
560.6
574.8
588.9
Reactive power reduction/saving
(4)
kVAr
106.3
104.0
101.8
Maximum Start Amps
A
795.9
810.1
824.2
Recommended Mains Fuse Size
A
670
670
710
Electronic Soft-start
Nominal Run Amps
A
625.8
637.8
649.9
Maximum Start Amps
A
741.9
753.9
766.0
Recommended Mains Fuse
A
670
670
710
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
560.6
574.8
588.9
Maximum Start Amps
A
676.7
690.9
705.0
Recommended Mains Fuse Size
A
670.0
670.0
710.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
35.0
35.0
Unit Nominal Run Amps
A
654.3
672.8
684.9
Recommended Mains Fuse Size
A
710
710
710
Motor Rating
kW
16.4
20.3
20.3
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
41.5
41.5
Unit Nominal Run Amps
A
660.8
679.3
691.4
Recommended Mains Fuse Size
A
710
710
750
Motor Rating
kW
20.3
23.9
23.9
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
33.2
33.2
Unit Nominal Run Amps
A
646.5
663.6
675.8
Recommended Mains Fuse Size
A
710
710
710
Motor Rating
kW
16.8
20.7
20.7
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
39.2
39.2
Unit Nominal Run Amps
A
651.4
668.3
680.5
Recommended Mains Fuse Size
A
710
710
710
Motor Rating
kW
20.7
24.4
24.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet