ELECTRICAL DATA

64

65

66

Unit Data

DCF050DX-13DXY0

DCF053DX-13DPY0

DCF055DX-14DPV0

Nominal Run Amps

(1)

A

301.3

307.9

335.2

Maximum Start Amps

A

537.9

543.2

570.5

Recommended Mains Fuse Size

A

355

355

355

Evaporator
Immersion Heater Rating

W

170

170

170

Condenser Fan - Per Fan (AC)
Quantity

13

13

14

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

13

13

14

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Compressor - Per Compressor
Nominal Run Amps

A

37.1 / 47.5

59.2 / 47.5

59.2 / 55.2

Quantity

3 + 3

2 + 3

2 + 3

Motor Rating

kW

23.5 / 29.6

36.2 / 29.6

36.2 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

210 / 287

298 / 287

298 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

283.5

285.3

304.6

Reactive power reduction/saving

(4)

kVAr

32.2

39.4

51.4

Maximum Start Amps

A

520.1

520.6

539.9

Recommended Mains Fuse Size

A

355

355

355

Electronic Soft-start
Nominal Run Amps

A

301.3

307.9

335.2

Maximum Start Amps

A

423.1

424.0

451.3

Recommended Mains Fuse

A

355

355

355

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

283.5

285.3

304.6

Maximum Start Amps

A

405.3

401.4

420.7

Recommended Mains Fuse Size

A

355

355

355

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

14.8

14.8

14.8

Unit Nominal Run Amps

A

316.0

322.6

350.0

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

8.4

8.4

8.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

21.2

21.2

21.2

Unit Nominal Run Amps

A

322.3

329.0

356.4

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

12.1

12.1

12.1

Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

13.9

13.9

13.9

Unit Nominal Run Amps

A

312.5

318.9

346.1

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

8.6

8.6

8.6

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

19.8

19.8

19.8

Unit Nominal Run Amps

A

317.4

323.7

350.8

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

12.4

12.4

12.4

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data Extra Quiet