Chillers deltachill™ air cooled and freecool, Te ch ni ca l, Air c oo led – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 248: Dcc electrical data - extra quiet
248
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
ni
ca
l
Chillers
DeltaChill™ Air Cooled and FreeCool
A
ir C
oo
led
ELECTRICAL DATA
152
153
154
Unit Data
DCC052DX-14EYY0
DCC054DX-13DYV0
DCC057DX-14DVV0
Nominal Run Amps
(1)
A
336.0
358.3
385.8
Maximum Start Amps
A
572.6
586.7
594.2
Recommended Mains Fuse Size
A
355
400
450
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (AC)
Quantity
14
13
14
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.3
1.3
1.3
Condenser Fan - Per Fan (EC)
Quantity
14
13
14
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 47.5
47.5 / 55.2
55.2 / 55.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
29.6 / 29.6
29.6 / 33.1
33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 287
287 / 267
267 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
314.2
329.6
348.8
Reactive power reduction/saving
(4)
kVAr
38.9
49.4
61.4
Maximum Start Amps
A
550.8
558.0
557.2
Recommended Mains Fuse Size
A
355
400
450
Electronic Soft-start
Nominal Run Amps
A
336.0
358.3
385.8
Maximum Start Amps
A
457.8
471.9
487.4
Recommended Mains Fuse
A
355
400
450
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
314.2
329.6
348.8
Maximum Start Amps
A
436.0
443.2
450.4
Recommended Mains Fuse Size
A
355
400
450
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
8.9
Unit Nominal Run Amps
A
344.5
366.9
394.4
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
4.4
4.4
4.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
347.0
369.3
396.9
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
6.1
6.1
6.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
7.3
7.3
7.3
Unit Nominal Run Amps
A
341.8
364.0
391.4
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
4.5
4.5
4.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
10.1
10.1
10.1
Unit Nominal Run Amps
A
344.1
366.2
393.6
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
6.3
6.3
6.3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Extra Quiet